Thermo Pride Spirit Gas TG8S Single Stage PSC 80% User Manual

Page 18

Advertising
background image

998491-UIM-B-1013

18

Johnson Controls Unitary Products

Air Supply Openings and Ducts

1. An opening may be used in lieu of a duct to provide the outside air

supply to an appliance unless otherwise permitted by the authority
having jurisdiction. The opening shall be located within 12” (30.5
cm) horizontally from, the burner level of the appliance. Refer to
“COMBUSTION AIR SOURCE FROM OUTDOORS and VENT
AND SUPPLY AIR SAFETY CHECK” in these instructions for addi-
tional information and safety check procedure.

2. The duct shall be either metal, or a material meeting the class 1

requirements of CAN4-S110 Standard for Air Ducts.

3. The duct shall be least the same cross-sectional area as the free

area of the air supply inlet opening to which it connects.

4. The duct shall terminate within 12 in (30.5 cm) above, and within 24

in (61 cm) horizontally from, the burner level of the appliance having
the largest input.

5. A square or rectangular shaped duct shall only be used when the

required free area of the supply opening is 9 in

2

(58.06 cm

2

) or

larger. When a square or rectangular duct is used, its small dimen-
sion shall not be less than 3 in (7.6 cm).

6. An air inlet supply from outdoors shall be equipped with a means to

prevent the direct entry of rain and wind. Such means shall not
reduce the required free area of the air supply opening.

7. An air supply inlet opening from the outdoors shall be located not

less than 12” (30.5 cm) above the outside grade level.

Combustion Air Source from Outdoors

1. Two permanent openings, one within 12 in (30.5 mm) of the top and

one within 12 in (30.5 mm) of bottom of the confined space, Two
permanent openings, shall communicate directly or by means of
ducts with the outdoors, crawl spaces or attic spaces.

2. One permanent openings, commencing within 12 in (30.5 mm) of

the top of the enclosure shall be permitted where the equipment has
clearances of at least 1 in (2.54 cm) from the sides and back and 6
in (15.24 cm) from the front of the appliance. The opening shall
communicate directly with the outdoors and shall have a minimum
free area of:

a. 1 square in per 3000 Btu per hour (6.45 cm3 per 0.879 kW) of the

total input rating of all equipment located in the enclosure.

b. Not less than the sum of all vent connectors in the confined

space.

3. The duct shall be least the same cross-sectional area as the free

area of the air supply inlet opening to which it connects.

4. The blocking effects of louvers, grilles and screens must be given

consideration in calculating free area. If the free area of a specific
louver or grille is not known. Refer to Table 7 to estimate free area.

Ventilated Combustion Air

The ventilated attic space or a crawl space from which the combustion
air is taken must comply with the requirements specified in “AIR
SOURCE FROM OUTDOORS” in this instruction or in Section 5.3, Air
for Combustion and Ventilation of the National Fuel Gas Code, ANSI
Z223.1 (latest edition). This type installation requires two properly sized
pipes. One brings combustion air from a properly ventilated attic space
or crawl space and a second pipe that extends from the furnace vent
connection (top right of unit) to the exterior of the building.

Vent and Supply (Outside) Air Safety Check Procedure

For Category I furnaces, vent installations shall be in accordance with
Parts 7 and 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
and or Section 7 and Appendix B of the CSA B149.1, Natural Gas and
Propane Installation Codes, the local building codes, furnace and vent
manufacture's instructions.

When a Category I furnace is removed or replaced, the original vent-
ing system may no longer be correctly sized to properly vent the
attached appliances.
An improperly sized vent system can cause CARBON MONOXIDE to
spill into the living space causing personal injury, and or death.

Table 8: Unconfined Space Minimum Area

BTUH Input Rating

Minimum Free Area

Required for Each Opening

40,000

40 in

2

(258 cm

2

)

60,000

60 in

2

(387 cm

2

)

80,000

80 in

2

(516 cm

2

)

100,000

100 in

2

(645 cm

2

)

120,000

120 in

2

(742 cm

2

)

130,000

130 in

2

(838 cm

2

)

Table 9: Free Area

BTUH Input

Rating

Minimum Free Area Required for Each Opening

Horizontal Duct

(2,000 BTUH)

Vertical Duct or

Opening to Outside

(4,000 BTUH)

Round Duct

(4,000 BTUH)

40,000

20 in

2

(129 cm

2

)

10 in

2

(64 cm

2

)

4” (10 cm)

60,000

30 in

2

(193 cm

2

)

15 in

2

(97 cm

2

)

5” (13 cm)

80,000

40 in

2

(258 cm

2

)

20 in

2

(129 cm

2

)

5” (13 cm)

100,000

50 in

2

(322 cm

2

)

25 in

2

(161 cm

2

)

6” (15 cm)

120,000

60 in

2

(387 cm

2

)

30 in

2

(193 cm

2

)

7” (18 cm)

130,000

65 in

2

(419 cm

2

)

33 in

2

(213 cm

2

)

7” (18 cm)

EXAMPLE: Determining Free Area.
Appliance

1 Appliance

2 Total Input

100,000

+ 30,000 = (130,000

 4,000) = 32.5 Sq. In. Vertical

Appliance

1 Appliance

2 Total Input

100,000

+ 30,000 = (130,000

 2,000) = 65 Sq. In. Horizontal

FIGURE 24: Outside and Ambient Combustion Air

Gable
Vent

Gas
Vent

Soffit
Vent

Ventilated

Attic

Top Above
Insulation

Optional
Inlet (a)

Outlet
Air (a)

Ventilated

Crawl Space

Gas
Water
Heater

Furnace

Soffit
Vent

Gas
Water
Heater

Inlet
Air (a)

Inlet
Air (b)

Furnace

Gas
Vent

Outlet
Air (a)

Outlet
Air (b)

Inlet
Air (a)

Inlet
Air (b)

Gas
Water
Heater

Furnace

Ventilated

Attic

Top Above
Insulation

Gable
Vent

Gas
Vent

Advertising