Ductwork, Louver sizing guidelines – Energy Tech Laboratories DSH User Manual

Page 11

Advertising
background image

FORM 145.32-IOM1 (908)

11

JOHNSON CONTROLS

DUCTWORK

When installing ductwork, adhere to local Codes and

sensible practice. Minimize duct runs and avoid abrupt

changes in direction where possible. Allow ample access

space for servicing of the coils and changing of filters.

Perform regular maintenance on ducts to increase unit

life, maintain efficient operation, and reduce accumu-

lation of explosive dust. Refer to blower performance

charts, and engineer duct runs and accessory pres-

sure drop so as not to exceed maximum external static

values.

LOUVER SIZING GUIDELINES

One of the key issues in obtaining optimum performance

from indoor air-conditioners is the proper selection of the

condenser intake and discharge louvers. Unlike outdoor

air cooled units, which intake and discharge their cooling

virtually unrestricted, indoor units must overcome the

resistance of grilles or louvers at the outside wall - plus

the restriction of any interconnecting ductwork.

Our indoor air cooled air-conditioners are designed to ac-

commodate the external static pressure loss associated

with properly sized louvers of the “storm proof” type. This

type of louver typically has a free area approximately

40-45% of the actual louver size. To determine the free

area required for any given unit, adhere to the following

guidelines:

- Size condenser air intakes for 500-750 feet/minute

nominal velocity

(Maximum recommended 800 feet/minute)
- Size condenser air discharge for 1,200-1,500 feet/

minute nominal velocity

(Maximum recommended 1,700 feet/minute)

The use of louvers with higher velocities than above may

be employed, at the discretion of the engineer/installer,

provided that the total air pressure drop does not exceed

the capability of the condenser fan and motor. The use

of low restriction louvers with shallow blade angles can

allow higher face velocities without excessive static

pressure loss.

Exceeding the static pressure capability of the con-

denser fan will result in insufficient condenser air volume.

This will cause a loss in system capacity, and may cause

compressor shutdown during high ambient periods. (In-

stallation of an oversize condenser motor/drive, where

applicable, may be considered in such cases.)

(As a general rule, these velocities will require an intake

louver sized approximately 1.25 to 1.5 times the dimen-

sions of the duct connection on the unit, and a discharge

louver sized approximately 1.5 to 2 times the duct con-

nection dimensions.)

Use only louver sections that provide different deflection

angles for air discharge and air intake, to ensure the

unit does not short circuit. Protect the unit from weather

conditions (rain, snow) entering through the condenser

air intake. All outdoor air ducts should pitch away from

the unit, toward the outside wall. Connect all ducts to unit

with canvas section duct connectors or choose another

suitable noise and vibration absorbing device.

The Manufacturer will not accept any

liability resulting from incorrect instal-

lation of this equipment. Follow instal-

lation instructions carefully.

Advertising