General information – Energy Tech Laboratories DSH User Manual

Page 4

Advertising
background image

JOHNSON CONTROLS

4

FORM 145.32-IOM1 (908)

GENERAL INFORMATION

Our units are designed to meet the ever-changing

(unique) installation requirements of today’s market. The

horizontal configuration is unitized for single package

or split installation. Low profile design allows the unit to

be installed on the floor or suspended from the ceiling.

All unit components are securely mounted inside the

heavy gauge “Galvalume” sheet metal cabinet. All units

are lined with a 1/2 in. thick – 21lb density acoustical

insulation to ensure the quietest operation. All models

are shipped with medium-efficiency 2-in. thick throw-

away filters. Multi-position filter rack is external to the

cabinet.

Unit can be turned on its side for short periods of time,

which allows passage through standard door sizes.

Removal of the cross supports on the top and sides will

convert packaged unit into a split system, allowing the

condensing section to be installed remotely from the

evaporator section.

Horizontal units 2, 3, 4 & 5 ton models have a single

refrigerant circuit configuration. All models are equipped

with an adjustable thermal expansion valve (with exter-

nal equalizer), one valve per circuit. Each refrigerant

circuit is also equipped with a liquid line filter drier, sight

glass/moisture indicator and easy access service gauge

ports. All 2-5 ton models are shipped as factory-charged

unitized packages. The 2-5 ton units include refrigerant

line shut-off valves to allow the units to be field split.

Installation time is minimized with all models. When plan-

ning an installation consider power supply, thermostat,

condensate drain line, duct run, servicing allowances,

and load points. A remote thermostat control device is

field supplied and installed to control the units operation.

Each refrigerant circuit is equipped with auto-reset high

pressure and low pressure switches. Each circuit is con-

stantly monitored by ComfortAlert module. By monitoring

and analyzing data from the Copeland Scroll compressor

and the thermostat demand, the module can accurately

detect the cause of electrical and system related failures

and protect the compressor. A flashing LED indicator

communicates the ALERT code and guides the service

technician more quickly and accurately to the root cause

of a problem. Control circuit is 24-volt operation with

oversized transformer. Optional anti-short circuit timers

can be field/factory installed.

Service access doors are equipped with handles and

are located on all sides of the unit to allow easy servic-

ing of all components. Service access doors are factory

shipped with knock-outs allowing gauge lines to be

installed and pressure readings to be taken while the

machine is operating. In addition there is a removable

panel on the access door so visual observation of the

sight glass is possible without removing the access door.

All units are equipped with centrifugal blowers combined

with variable pitch adjustable pulleys. Forward curved

double width and inlet centrifugal blowers are used for

condenser & evaporator air movement. All models em-

ploy a draw-through air flow system. All blower wheels

are galvanized steel, with solid steel shafts and are

equipped with permanently lubricated ball bearings. V-

belt driven blowers are used in all models; RPM can be

adjusted through the variable pitch motor sheave.

ONLY QUALIFIED PERSONNEL SHOULD

PERFORM INSTALLATION AND SER-

VICE OF THIS EQUIPMENT.

High efficiency scroll compressors are used in all mod-

els, mounted on durable rubber isolator pads reducing

vibration and noise while operating. Large evaporator

and condenser coil face areas reduce noise levels, air

pressure drops and minimize potential for condensate

blow off. All models are equipped with copper tube and

rippled aluminum plate fin coils.

Units will operate reliably at an outdoor ambient down

to 60 deg F.