Standard motors, Fan performance data, Supply air blower performanceexternal – Energy Tech Laboratories DSH User Manual

Page 13: Condenser air blower performance

Advertising
background image

FORM 145.32-IOM1 (908)

13

JOHNSON CONTROLS

STANDARD MOTORS

MODEL

VOLTAGE

COMPRESSOR

EVAPORATOR FAN

CONDENSER FAN

MIN. CCT.

"MOP"

#

QTY

RLA

LRA

HP

FLA

HP

FLA

AMPACITY

Max Overcurrent

Prot.

AC024H12 208-230/1/60

1 @ 13.5

58.3

0.25

2.6

0.50

4.5

23.98

35

AC024H32 208-230/3/60

1 @ 8.6

55.0

0.25

1.4

0.50

2.2

14.35

20

AC036H12

208-230/1/60

1 @ 14.1

77.0

0.33

3.3

0.75

5.5

26.43

40

AC036H32

208-230/3/60

1 @ 9.0

71.0

0.33

1.6

0.75

2.6

15.45

20

AC036H34

460/3/60

1 @ 5.6

38.0

0.33

0.8

0.75

1.3

9.10

15

AC036H35

575/3/60

1 @ 3.8

36.5

0.50

0.9

0.75

1.0

6.63

15

AC048H12

208-230/1/60

1 @ 19.9

109.0

0.75

5.5

1.00

6.3

36.68

50

AC048H32

208-230/3/60

1 @ 13.1

83.1

0.75

2.6

1.00

3.3

22.28

35

AC048H34

460/3/60

1 @ 6.1

41.0

0.75

1.3

1.00

1.5

10.43

15

AC048H35

575/3/60

1 @ 5.0

34.0

0.75

1.0

1.00

1.1

8.35

15

AC060H32

208-230/3/60

1 @ 16.0

110.0

1.00

3.3

1.50

4.6

27.90

40

AC060H34

460/3/60

1 @ 7.8

52.0

1.00

1.5

1.50

2.1

13.35

20

AC060H35

575/3/60

1 @ 5.7

38.9

1.00

1.1

1.50

1.7

9.93

15

Notes:

Data shown for packaged unit installation, with single point power supply.
For split installation with separate evaporator motor power supply, calculate MCA and MFS as follows -
Min. Circuit Ampacity ( MCA ) = 1.25 X Largest motor amps (FLA or RLA) + sum of the remaining motor amps

Max Fuse / Cct. Bkr Size ( MFS ) = 2.25 X Largest motor amps + sum of the remaining motor amps

Select next smallest NEC listed fuse size from calculated value

FAN PERFORMANCE DATA

SUPPLY AIR BLOWER PERFORMANCE

EXTERNAL STATIC PRESSURE - Inches W.C.

MODEL

SUPPLY

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

700

593 0.06 755 0.10 915 0.13 1048 0.17 1175 0.23

-

-

-

-

-

-

-

-

2 TON

800

629 0.08 777 0.12 914 0.16 1169 0.20 1178 0.25

-

-

-

-

-

-

-

-

900

668 0.11 804 0.15 930 0.19 1170 0.24

-

-

-

-

-

-

-

-

-

-

1000

598 0.11 722 0.16 835 0.19 930 0.25 1141 0.32

-

-

-

-

-

-

-

-

3 TON

1200

727 0.20 831 0.25 929 0.31 972 0.33

-

-

-

-

-

-

-

-

-

-

1400

747 0.26 844 0.32

-

-

-

-

-

-

-

-

-

-

-

-

-

-

1450

595 0.22 661 0.27 745 0.31 836 0.38 909 0.45 982 0.52 1046 0.61

-

-

-

-

4 TON

1600

601 0.26 691 0.33 773 0.39 847 0.44 921 0.51 987 0.61 1056 0.67

-

-

-

-

1800

652 0.35 735 0.42 812

0.5

883 0.57 948 0.64 1018 0.72

-

-

-

-

-

-

1800

583 0.30 674 0.37 755 0.44 830 0.52 900 0.59 966 0.69 1037 0.75

-

-

-

-

5 TON

2000

688 0.45 767 0.53 839 0.61 907 0.69 971 0.77 1029 0.85 1086 0.92

-

-

-

-

2200

677

0.5

754 0.59 826 0.68 894 0.77 957 0.86 1018 0.95

-

-

-

-

-

-

NOTE:

1. At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur. Adjust airflow downward as necessary.
2. Values include pressure drop from wet coil and clean filters.
3. Shaded areas indicate oversize motors
4. Adjustment limits of standard factory-installed drives are indicated by bold borders. (See pulley data on Pg. 17)

CONDENSER AIR BLOWER PERFORMANCE

EXTERNAL STATIC PRESSURE - Inches W.C.

MODEL OUTDOOR

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2 TON

1600

750 0.29 852 0.35 948 0.42 996 0.46

-

-

-

-

-

-

-

-

3 TON

1950

864 0.47 949 0.55 1032 0.63 1112 0.72

-

-

-

-

-

-

-

-

4 TON

2500

645 0.53 749 0.63 812 0.74 872 0.86 945 0.98

-

-

-

-

-

-

5 TON

2900

723 0.79 800 0.84 871 1.07 935 1.20 996 1.55 1057 1.42

-

-

-

-

DSH

DSH

DSH

DSH

DSH

DSH

DSH

DSH

DSH

DSH

DSH

DSH
DSH