ILX34-AENWG ♦ Point I/O Platform

User Manual

Wireless POINT I/O Adapter

Page 52 of 177

ProSoft Technology, Inc.

August 16, 2013

4 Click the C

ONNECTION

tab, and then change the RPI value for the module

from 20 (the default) to 50 (the recommended value for analog or specialty
modules). This value determines how often to exchange data with the ILX34-
AENWG adapter.

Important: To avoid overloading the ILX34-AENWG adapter, we recommend that RPI be no less

than 10 ms for rack connections and 50 ms for direct connections.

5 Click OK

save the configuration.

The following illustration shows the I/O Configuration for this project.

3.4.2 Add the Digital Output Module and Configure for Rack

Optimization

1 Right-click the ILX34-AENWG adapter under the I/O Configuration folder and

select N

EW

M

ODULE

.