Modbus tcp/ip – ProSoft Technology 5201-MNET-ASCII User Manual

Page 12

Advertising
background image

Functional Overview

MNET ♦ ProLinx Gateway

Driver Manual

Modbus TCP/IP Interface Module

Page 12 of 78

ProSoft Technology, Inc.

September 1, 2010

1.3

Modbus TCP/IP

ProSoft’s Modbus TCP/IP implementation uses the module’s shared internal
memory for data transfer. Sharing the memory with another protocol driver allows
the module to transfer data between Modbus TCP/IP devices and other devices
on other networks.

Configurable floating-point data movement is supported, including support for
Enron or Daniel

®

floating-point applications.

Modbus TCP/IP Server (Slave)
The server driver accepts incoming connections on Service Port 502 for clients
using Modbus TCP/IP MBAP messages and from clients on Service Port 2000
(or other Service Ports) for clients using Encapsulated Modbus messages..
 Supports five independent server connections for Service Port 502 (MBAP)
 Supports five independent server connections for Service Port 2000

(Encapsulated)

 Supports a total Modbus TCP/IP data transfer capacity of up to 4000

registers or up to 64,000 bits in any combination of data types throughout the
memory database

 Modbus data types overlap in the gateway’s memory database, so the same

data can be conveniently read or written as bit-level or register-level data.

Modbus TCP/IP Client (Master)
 Actively reads data from and writes data to Modbus TCP/IP devices, using

MBAP or Encapsulated Modbus message formats

 Offers one client connection with up to 100 commands to talk to multiple

severs

Status Data
Error codes, counters, and port status available

Advertising