Preset single register (function code 06) – ProSoft Technology 5201-MNET-ASCII User Manual

Page 61

Advertising
background image

MNET ♦ ProLinx Gateway

Modbus Protocol Specification

Modbus TCP/IP Interface Module

Driver Manual

ProSoft Technology, Inc.

Page 61 of 78

September 1, 2010

4.6

Preset Single Register (Function Code 06)

Query
Function (06) allows the user to modify the contents of a holding register. Any
holding register that exists within the controller can have its contents changed by
this message. However, because the controller is actively scanning, it also can
alter the content of any holding register at any time. The values are provided in
binary up to the maximum capacity of the controller unused high order bits must
be set to zero. When used with Server address zero (Broadcast mode) all Server
controllers will load the specified register with the contents specified.

Note Functions 5, 6, 15, and 16 are the only messages that will be recognized as valid for

broadcast.

Adr

Func Data Start Reg

Hi

Data Start Reg

Lo

Data #of Regs Hi Data #of Regs Lo Error Check Field

11

06

00

01

00

03

CRC

Response
The response to a preset single register request is to re-transmit the query
message after the register has been altered.

Adr

Func Data Reg Hi Data Reg Lo Data Input Reg Hi

Data Input Reg Lo Error Check Field

11

06

00

01

00

03

CRC