Slave address, Modbus function – ProSoft Technology 5201-MNET-ASCII User Manual

Page 29

Advertising
background image

MNET ♦ ProLinx Gateway

Modbus TCP/IP Protocol Configuration

Modbus TCP/IP Interface Module

Driver Manual

ProSoft Technology, Inc.

Page 29 of 78

September 1, 2010

2.5.10 Slave Address

0 - Broadcast to all nodes

1 to 255

Use this parameter to specify the slave address of a remote Modbus Serial
device through a Modbus Ethernet to Serial converter.

Note: Use the Node IP Address parameter (page 28) to address commands to a remote Modbus

TCP/IP device.

Note: Most Modbus devices accept an address in the range of only 1 to 247, so check with slave

device manufacturer to see if a particular slave can use addresses 248 to 255.

If the value is set to zero, the command will be a broadcast message on the network. The Modbus

protocol permits broadcast commands for write operations. Do not use node address 0 for read

operations.

2.5.11 Modbus Function

1, 2, 3, 4, 5, 6, 15, or 16

This parameter specifies the Modbus Function Code to be executed by the
command. These function codes are defined in the Modbus protocol. The
following table lists the purpose of each function supported by the module. More
information on the protocol is available from www.modbus.org.

Modbus Function Code

Description

1

Read Coil Status

2

Read Input Status

3

Read Holding Registers

4

Read Input Registers

5

Force (Write) Single Coil

6

Preset (Write) Single Register

15

Force Multiple Coils

16

Preset Multiple Registers