Installation, Functional test, Continued) – Emerson ASCO 7000 User Manual

Page 4: Harnesses, Engine starting contacts, Auxiliary circuits, 1 – manual operation test

Advertising
background image

INSTALLATION

(continued)

1---2

Harnesses

The transfer switch is connected to the left side of the
controller by a plug-in harness (two plugs).

Engine Starting Contacts

The engine control contact connections (if used) are
located on the transfer switch. Connect signal wires to
appropriate terminals as specified in Table A and shown
in Figure 1-2.

Table A. Engine Start Connections

When normal

source fails

Terminals on

transfer switch

contact closes

TB14 and TB15

contact opens

TB14 and TB16

TB 14

TB 15

TB 16

ENGINE STARTING CONTACTS

( SHOWN DE–ENERGIZED )

TOP

STUD

MIDDLE

STUD

BOTTOM

STUD

14

15

16

TS

NR

NR

Figure 1-2. Engine starting contact label

and location on left side of transfer switch.

Auxiliary Circuits

Connect auxiliary circuit wires to appropriate terminals on
the transfer switch. Note the control features that are
furnished on this switch. Make the necessary auxiliary
connections by referring to the Wiring Diagram.

Functional Test

The Functional Test consists of three checks:

S

1 — Manual Operation Test, on this page

S

2 — Voltage Checks, page 1–3

S

3 — Electrical Operation, page 1–4

Do these checks in the order presented

to avoid damaging the ATS.

Read all instructions on the Wiring Diagram and labels
affixed to the automatic transfer switch. Note the
control features that are provided and review their
operation before proceeding.

1 – Manual Operation Test

A maintenance handle is provided on the Transfer Switch
for maintenance purposes only. Manual operation of the
transfer switch should be checked before it is energized
(operated electrically).

Do not manually operate the transfer switch

until both power sources are disconnected:

open both circuit breakers.

1. After deenergizing both power sources, open the

enclosure door. Locate and the maintenance handle
on the left side of the transfer switch. See Figure 1–3.

2. Grasp the attached maintenance handle and turn it

with thumb and fingers as shown to manually operate
it. The maintenance handle turns the opposite

direction of the weight. Turn it up or down as shown
to manually operate the transfer switch. It should
operate smoothly without any binding. If it does not,
check for shipping damage or construction debris.

3. Return the transfer switch to the Normal position.

Note: If Normal and Emergency connections are

reversed this operation is also reversed.

Now continue to 2 – Voltage Checks on next page.

maintenance

handle

With ALL POWER OFF grasp

maintenance handle and turn it

quickly with your thumb and fingers.

weight marked N (normal)

and E (emergency)

floating

weight

weight

Position of the transfer switch is indicated here

Figure 1–3. Maintenance handle and positions.