Installation – Emerson ASCO 7000 User Manual

Page 5

Advertising
background image

INSTALLATION

(continued)

1---3

RED

RED

GREEN

GREEN

observe

these lights

Figure 1-4. Standard controls and indicators.

2 – Voltage Checks

First check nameplate on transfer switch; rated voltage
must be the same as normal and emergency line voltages.

Verify that the feeders have been

connected to the proper lugs.

Use extreme caution when using a meter

to measure voltages. Do not touch power

terminals; shock, burns, or death could result !

Perform steps 1 through 6 at the right. Observe the
status lights. See Figure 1–4.

Q

Black square means light is on.

S

White square means light is off.

* If necessary, adjust voltage regulator on the generator
according to the manufacturer’s recommendations.
The Automatic Transfer Switch will respond only to the
rated voltage specified on the Transfer Switch
nameplate.

Note

Refer to Section 3 of Group 5 Controller User’s Guide
381333–126 for how to display the Status of the ATS
and the Voltage and Frequency of each source.

Now continue to 3 – Electrical Operation on next page.

1

Close the normal source circuit

breaker. The Transfer Switch

Connected To Normal and the

Normal Source Accepted lights

should come on.

2

Use an accurate voltmeter to

check phase to phase and

phase to neutral voltages pres-

ent at the transfer switch normal

source terminals.

3

Close the emergency source

circuit breaker. (Start generator,

if necessary.) The Transfer

Switch Connected To Normal &

Emergency Source Accepted

lights should come on.

4

Use an accurate voltmeter to

check phase to phase and

phase to neutral voltages pres-

ent at the transfer switch emer-

gency source terminals.*

5

Use a phase rotation meter to

check phase rotation of emer-

gency source; it must be the

same as the normal source.

A B C

6

Shut down the engine–genera-

tor, if applicable. The Emergen-

cy Source Accepted light should

go off. Then put the starting

control selector switch (on the

generator set) in the automatic

position. Close enclosure door.