Installation requirements and guidelines, Site guidelines, Site guidelines -1 – Enterasys Networks 7S4280-19-SYS User Manual

Page 29: Installation requirements and, Guidelines, Chapter 2

Advertising
background image

Enterasys NAC Controller Hardware Installation Guide 2-1

2

Installation Requirements and Guidelines

This chapter describes site guidelines that must be met before installing an 
Enterasys NAC Controller into a rack or cabinet, Enterasys NAC Controller configuration 
guidelines, and operating specifications for the Enterasys NAC Controller.

Site Guidelines

The following guidelines must be observed when a site is selected for the 
Enterasys NAC Controller. If the guidelines are not followed, unsatisfactory network performance 
may result.

To ensure proper ventilation and prevent overheating of the chassis in either the rackmounted 
or standalone configuration, there must be 5.1 centimeters (2 inches) of clearance on either 
side and in the rear of the unit.

To install the Enterasys NAC Controller as a freestanding unit on a shelf, the shelf must be 
able to support 13.6 kilograms (30 pounds) of static weight.

To install the Enterasys NAC Controller as a rackmounted unit, care must be taken to ensure 
that the rack used will support the unit and that the rack remains stable.

The power supplies for the Enterasys NAC Controller require two three‐pronged power 
receptacles capable of delivering the current and voltage specified in “

Power Supply

” on 

page A‐2. Two ac outlets on independently fused circuits are required for each power supply, 
and must be located less than 2 meters (6 feet) from the site. The power cord used and type of 
outlet is dependent on the country. In the United States, two power cords with NEMA 5‐15P 
plugs are provided with each power supply.

Ambient temperature at the installation site must be maintained between 5° and 40°C 
(41° to 104°F). Temperature changes must be maintained within 10°C (18°F) per hour. 

Electrical Hazard: Only qualified personnel should perform installation procedures.

Riesgo Electrico: Solamente personal calificado debe realizar procedimientos de instalacion.

Elektrischer Gefahrenhinweis: Installationen sollten nur durch ausgebildetes und qualifiziertes
Personal vorgenommen werden.

For information about...

Refer to page...

Site Guidelines

2-1

Configuration Guidelines

2-2

LANVIEW LEDs

2-2

NAC Controller PEP Network Requirements

2-3

Advertising
This manual is related to the following products: