9. Install the flex pipe assembly through the wall thimble, ensure that this portion of pipe slides through

the outside wall far enough to connect onto the vent termination cap.

10. Apply a bead of Mill-Pac Black sealant to the top section of the Ø4” (10 cm) by 5” (12.5 cm) flue collar

adaptor previously installed into the fireplace flue outlet. Slide the Ø4” (10 cm) flex vent over the flue

collar and secure with three (3) sheet metal screws evenly spaced.

11. Place a bead of high temperature silicone on the intake collar of the fireplace, slide the Ø6⅝” (16.25

cm) flex intake liner over the collar, secure the flex liner with three (3) sheet metal screws evenly

spaced.

12. On the outside of the exterior wall, apply a bead of Mill-Pac Black sealant to the Ø4” (10 cm) pipe of

the vent terminal. Slide the flex liner onto the vent terminal and secure with three (3) sheet metal

screws evenly spaced.

13. Place a bead of high temperature silicone on the intake collar of the vent terminal, slide the Ø6⅝”

(16.25 cm) flex intake liner over the collar, secure the flex liner with three (3) sheet metal screws

evenly spaced.

14. Attach the vent terminal to the outside of the house using four (4) wood screws provided.
15. Light the appliance and ensure proper operation.

o

theR

a

PPRoveD

v

ent

P

aRts

:

Table 3: Approved Vent Manufacturers

Manufacturer

Trade Name

Nominal Sizes

American Metal Products

AmeriVent Direct

4” - 6 5/8”

Security Chimneys International LTD

Secure Vent

4” - 6 5/8”

Selkirk Metalbestos

Direct-Temp

4” - 6 5/8”

Simpson Dura-Vent

Direct Vent GS

4” - 6 5/8”

The DV42DX fireplace has been tested and certified for use with AMERICAN METAL PRODUCTS

“AMERIVENT DIRECT”, SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SECURITY CHIMNEY’S

“SECURE VENT DIRECT VENT SYSTEM” and SELKIRK “DIRECT-TEMP VENT SYSTEM” kits are available

for horizontal and vertical venting. When using Simpson Duravent, it is recommended that, before

installation, a bead of RTV High Temperature Silicone should be applied to each outer vent joint, and Mil-

Pac to each inner joint. When planning an installation, it will be necessary to select the proper length of

vent pipe for the particular requirements.

WARNING: Do not mix parts from different vent manufacturers’s systems.
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a Direct Vent GS

starting collar in conjunction with Secure Vent, Direct-Temp, and Ameri Vent Direct venting systems. Use

of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the

Intertek WH listing of the appliance.

Initial Installation

QUALIFIED INSTALLERS ONLY

20