Initial installation – Enviro DV42DX User Manual

Page 28

Advertising
background image

For the first 24 inches (610 mm) of

ducting, ½ inch (13 mm) of clearance

is required. After 24 inches (610 mm),

the duct can be run with 0 inch (0 mm)

clearance, though ½ inch (13 mm) is

preferred. To avoid heat loss, insulate

the duct whenever it passes through an

unheated area (i.e. crawl space). Insulating

the ducts elsewhere helps the efficiency of

the ducting system.
Standard galvanized ducting and heat

registers are to be used. Simply remove

the desired cover plate from the outside of

the firebox and attach a 6 inches (152 mm)

starter ring. Make sure to foil-tape all seams

to prevent leaking. Ensure all ducting meets

local building codes.

Figure 38. Ducting Options; ducted from

upper floor to lower floor & from lower floor

to upper floor.

Figure 39. More Ducting Options; ducted to outside & to

another room on an interior wall.

Initial Installation

QUALIFIED INSTALLERS ONLY

D

ucting

:

The option of ducting allows heat from the fireplace to be transferred to a different area. The maximum

total length for the ducting is 20 feet (6.1 m). There are four (4) duct outlets that can be used (see Figure

37), however, the blower puts out 200 cfm no matter how many ducts are used. Therefore, the more

ducts there are, the less air goes through each one. A short, straight duct maximizes its heating ability

as air in the ducts is restricted by the length and number of bends in the pipe.

Figure 37. Heat Dumping Options.

28

Advertising
This manual is related to the following products: