Analog Input Modules

Figure 20 illustrates the basic signal processing operation. Analog signals from four separate channels are received by a multiplexer
(MUX). The MUX sequentially transfers this data to an analog-to-digital converter (ADC). The ADC measures the analog signal and
converts it to a digital value. This digital value is presented to the controller’s central processes unit (CPU). This data is then presented
to the QCPort for external processing.

Figure 20: Analog Input Module Operation

Analog input signal delays are associated with multiplexer switching, channel updating and channel reconfiguration. These delays are
all influenced by analog input filter frequency selection.

Table 24: Analog Input Signal Delays

Filter Setting

Total Update Time

50 Hz

336 ms

60Hz

283.2 ms

250 Hz

80 ms

500 Hz

44 ms

M

U

X

V0

I0

I1

V1

I2

V2

I3

C0

C1

C2

C3

V3

ADC

CPU

QC Port

V

1

+V

2

-V

2