Transmitter Orientation and Power Supply

2.5.1

DC power requirements for Model 2400S Analog and PROFIBUS-DP transmitters

If you are using DC power with a Model 2400S Analog or PROFIBUS-DP transmitter, the following
requirements apply:

At startup, the transmitter power source must provide a minimum of 1 A of short-term current
per transmitter.

Length and conductor diameter of the power cable must be sized to provide 18 VDC minimum
at the power terminals, at a load current of 0.5 A. (This assumes a single transmitter per cable.
Connecting multiple transmitters to a single cable should generally be avoided.) To size the
cable, refer to Table 2-1 and use the following formula as a guideline:

2.6

Wiring the power supply

Note: This procedure is required only for Model 2400S Analog and PROFIBUS-DP transmitters.

To wire the power supply:

1. Remove the transmitter housing cover and user interface module as described in Section 2.4.

2. Unscrew the warning flap screw and raise the warning flap. Figure 2-3 shows the warning flap

in the open position.

3. Connect the power supply wires to terminals 9 and 10, as shown in Figure 2-3.

4. Ground the power supply to the transmitter’s internal grounding screw, shown in Figure 2-3.

5. Lower the warning flap and tighten the warning flap screw.

Table 2-1

Typical power cable resistances at 68 °F (20 °C)

Gauge

Resistance

(1)

(1) These values include the resistance of both high and low conductors in a cable.

14 AWG

0.0050

Ω/foot

16 AWG

0.0080

Ω/foot

18 AWG

0.0128

Ω/foot

20 AWG

0.0204

Ω/foot

2,5 mm

2

0,0136

Ω/meter

1,5 mm

2

0,0228

Ω/meter

1 mm

2

0,0340

Ω/meter

0,75 mm

2

0,0460

Ω/meter

0,5 mm

2

0,0680

Ω/meter

Example

The transmitter is mounted 350 feet from a DC power supply. If you want to use
16 AWG cable, calculate the required voltage at the DC power supply as follows:

MinimumSupplyVoltage

18V

CableResistance

CableLength

×

0.5A

×

(

)

+

=

MinimumSupplyVoltage

18V

0.0080 Ohms/ft

350 ft

×

0.5A

×

(

)

+

=

MinimumSupplyVoltage

19.4V

=

MinimumSupplyVoltage

18V

CableResistance

CableLength

×

0.5A

Ч

(

)

+

=