Installation Manual

19

I/O Wiring – Model 2400S Analog Transmitters

P

o

wer Su

ppl

y

I/O
W
irin
g

– DP

an
d

DN

I/

O W

iri

n

g

– AN

Be
fo

re
Y

o

u

Begin

3.4.4

Discrete input wiring

Discrete input wiring depends on whether you will use internal or external power. The following
diagrams are examples of proper wiring for these configurations:

Internal power – Figure 3-13

External power – Figure 3-14

If external power is configured, power may be supplied by a PLC or other device, or by direct DC
input. See Table 3-2 for input voltage ranges.

Figure 3-13

Discrete input wiring – Internal power

Figure 3-14

Discrete input wiring – External power

Table 3-2

Input voltage ranges for external power

VDC

Range

3–30

High level

0–0.8

Low level

0.8–3

Undefined

+

PLC or

other device

OR

VDC
(see Table 3-2

)

Direct DC input
(see Table 3-2

)

+

+