New installation, Flush-mounted aquastat replacement, Well-mounted aquastat replacement – Honeywell L7224A User Manual

Page 3

Advertising
background image

L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT

®

CONTROLLERS

3

68-0281EFS—06

IMPORTANT

Immersion well must fit sensing element and

sensor must rest against bottom of well.

New Installation

Order well assemblies separately; see Table 1 and form

no. 68-0040, Immersion Wells and Compression Fittings

for Temperature Controllers. Boilers usually have tappings

that allow the well to be mounted horizontally so boiler

water of average temperature can circulate freely over the

well.

1. Turn off all power and drain the boiler, if applicable.

2. If no tapping is provided, prepare properly sized and

threaded tapping near the top of the boiler.

3. Sparingly coat the well threads with pipe dope.

NOTE: Do not attempt to tighten by using the case

as a handle.

4. Install the well in the boiler tapping and tighten

securely.

5. Refill boiler and check for water leakage.

6. Loosen but do not remove the well clamp screw.

7. Fit the case into the well so the clamp on the case

slides over the flange on the well.

8. Securely tighten the clamp screw.

9. Insert the sensor element into the well until it bot-

toms. See Replacement Sensor Installation section

for details. (If necessary, slightly bend the wire

inside the case to hold the sensor against the bot-

tom of the well.)

10. Turn power ON.

11. Set High Limit, Low Limit and Low Limit Differential

to the settings recommended by the boiler OEM.

(See OPERATION section.) (See INSTALLATION

steps 6 and 7.)

12. On L7248L models, adjust ELL option to match your

configuration (see OPERATION section, and Fig. 11

and 13).

IMPORTANT

Best thermal response is obtained with a well

that snugly fits the sensor. Insert the sensor until

it rests against the bottom of the well. Use a well

of correct length and bend the wiring, if neces-

sary, to hold the bulb against the bottom of the

well.

If the well is not a snug fit on the sensor, use the

heat-conductive compound (furnished with

TRADELINE

®

models) as follows: Fold the

plastic bag of compound lengthwise and twist it

gently. Then snip off end of bag and work the

open end of the bag all the way into the well.

Slowly pull out the bag while squeezing it firmly

to distribute compound evenly in the well. Bend

the wiring, if necessary, to hold the sensor

against the bottom of the well and to hold outer

end of the sensor in firm contact with the side of

the well. See Fig. 2. Wipe excess compound

from the outer end of the well.

Fig. 2. Position of sensor in immersion well.

Flush-Mounted Aquastat

Replacement

Turn off all power and remove the old control. Refer to the

cover insert of the old control to identify and tag each

external lead as it is disconnected. If the old well is

unsuitable for the new installation, remove it and replace it

with a suitable new well. If the old well is suitable, use it.

Well-Mounted Aquastat

Replacement

Turn off all power and remove the old control. Refer to the

cover insert of the old control to identify and tag each

external lead as it is disconnected. If the old well is

unsuitable for the new installation, remove it and proceed

with instructions for new installation. If the old well is

suitable, use it.

1. Loosen, but do not remove, the well clamp screw on

the side of the control case.

2. Position immersion well clamp snugly over the

flange of the adapter and tighten the clamp screw.

3. Insert the sensor into the well as shown in Fig. 2 or

3. (See Replacement Sensor Installation section for

details.)

Fig. 3. Circuit board, showing sensor connection and

well holes for horizontal mount models.

SENSOR WIRES

IMMERSION WELL

CLAMP SCREW

IMMERSION

WELL CLAMP

M16120

HEAT-CONDUCTIVE COMPOUND

(OPTIONAL)

CONTROLLER CASE

BOILER

IMMERSION

WELL

SENSOR

C1

B1

ZC

L2

LINE

C2

ZR

L1

B2

T

T3

2

1

THERMOSTAT

TERMINALS

ENVIRACOM

TM

TERMINALS

SENSOR HOLES

FUSE

M32186

SENSOR

CONNECTOR

DISPLAY

Advertising