Replacement sensor installation, Fuse, Wiring – Honeywell L7224A User Manual

Page 4: Operation, General, Warning

Advertising
background image

L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT

®

CONTROLLERS

68-0281EFS—06

4

Fig. 4. Replacement sensor installation.

Replacement Sensor Installation

Turn off all power and:

1. Carefully disconnect sensor from circuit board by

pulling gently on the connector.

2. Gently pull sensor from thermo well and through cir-

cuit board by pulling on leadwires.

3. Carefully align replacement sensor with hole in cir-

cuit board and guide through Aquastat case and

into well. (See Fig. 5).

4. Make sure sensor is fully seated to bottom of well

(See Fig. 4). Use a small pencil to measure depth of

sensor in well, if necessary.

5. Connect sensor to circuit board by pressing con-

nector on sensor unit into mating connector on cir-

cuit board (See Fig. 5).

6. For remote sensors (flush-mounted Aquastat Con-

trollers) be sure to use 121571AA Clamp (see

Accessories) to securely hold sensor in place.

Fig. 5. Circuit board, showing sensor connection and

well holes for vertical mount models.

Fuse

The 1 Amp fuse located near the transformer is intended

to protect the EnviraCOM circuit from incorrect wiring. The

Aquastat will continue to function should the fuse blow or

be removed though no EnviraCOM communication will be

possible on the bus and Err 6 will be displayed. See

Table 10.

WIRING

WARNING

Electrical Shock Hazard.

Can cause serious injury or death.

Disconnect power supply before making wiring

connections to prevent electrical shock or

equipment damage.

All wiring must comply with local electrical codes and

ordinances. Do not exceed the specifications in the

Application section when wiring this control. Use wire

rated for 194 °F (90 °C) or higher.

IMPORTANT

The terminals on these Aquastat Controllers are

approved for use with copper wire only.

Follow the appropriate wiring diagrams shown on the

inside of the front cover of the L7224A,C; L7248A,C,L or

in Fig. 8–13.

Refer to Fig. 6 for Connections for the optional Outdoor

Reset Module and the Domestic Hot Water (DHW)

module. In subsequent wiring diagrams these modules

will be displayed with a dotted line signifying that they are

optional.

Fig. 6. Wiring the Outdoor Reset Module and the

Domestic Hot Water Module.

OPERATION

General

The L7224A,C and L7248A,C,L Oil Electronic Aquastat

Controllers are primary safety limit-rated devices

designed for use with oil fired boilers with line voltage

burners and circulators. Many boilers do not include

wiring or control compartments as part of the design, but

are provided with an integral, replaceable, immersion well

that is the mounting hardware for the Aquastat

Controllers. Wiring to the other controls is done through

flexible metal conduit.

For boilers that do include a remotely (flush) mounted

control, the wiring may be completed with conduit or

routed behind the boiler sheet metal.

SENSOR WIRES

M22026

HEAT-CONDUCTIVE COMPOUND

(OPTIONAL)

BOILER

IMMERSION

WELL

SENSOR

C1

B1

ZC

L2

LINE

C2

ZR

L1

B2

T
T 3

2
1

THERMOSTAT

TERMINALS

ENVIRACOM

TM

TERMINALS

DISPLAY

SENSOR

CONNECTOR

SENSOR HOLES

FUSE

RELAYS

M32187

C1

B1

ZC

L2

LINE

C2

ZR

L1

B2

T
T

3

2
1

1 2 3 OT OT

C7089U1006

OUTDOOR

SENSOR

50022037-002

OUTDOOR

RESET MODULE

1 2 3 TS TS

50022037-005

DOMESTIC HOT

WATER MODULE

32003971-003

TEMPERATURE

SENSOR

M29651