L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT

®

CONTROLLERS

5

68-0281EFS—06

A separate electromechanical high-limit is not required in

a system that uses this control to meet Underwriters

Laboratories Inc. requirements for oil-fired boiler

assemblies, UL 726.

On the L7224 models, the High Limit, Low Limit, Low Limit

Differential, and Anti Short-Cycle time can be adjusted to

the setting recommended by the boiler OEM. On the

L7248 models, the High Limit, and Anti Short-Cycle time

are also adjustable, see “Adjusting Settings”.

The overall range of the High Limit is from 130 °F to

240 °F (54 °C to 116 °C). Select devices may have

different ranges. Some models have limited ranges on the

High Limit setpoint; this limited range is listed on the

device label.

Some models also have a Low Limit and Low Limit

Differential adjustment. The range of the Low Limit is from

110 °F to 220 °F (43 °C to 104 °C). Select devices may

have different ranges.

The Zr setting can be set to DHW, Zoning, or for tankless

coil applications depending on the L7224/L7248.

If a W8735S1000 AquaReset™ Outdoor Reset Module is

installed, the reset curve can be set by entering the

minimum outdoor temperature, minimum (boiler)

temperature, and maximum outdoor temperature on the

3-digit display. The range of the minimum outdoor

temperature is from -40 °F to 40 °F (-40 °C to 4.4 °C) and

has a default setting of 0 °F (-18 °C). The range of the

maximum outdoor temperature is from 30 °F to 70 °F

(-1.1 °C to 21.1 °C) and has a default setting of 40 °F. The

range of the minimum (water or boiler) temperature is

from 80 °F to 180 °F (26.7 °C to 82.2 °C) and has a

default setting of 130 °F. See the “Outdoor Reset Module”

Installation Instructions (form number 69-2335) for more

information on setting the boiler reset curve and all related

parameters.

The L7224A,C and L7248A,C,L are designed for use with

24 Vac electronic and electromechanical thermostats or

EnviraCOM™ enabled thermostats, and have screw-type

terminals for easy field connection.

Adjusting Settings

To discourage unauthorized changing of Aquastat

settings, a procedure to enter the

ADJUSTMENT mode is

required. To enter the

ADJUSTMENT mode, press the

UP, DOWN, and I buttons (Refer to Fig. 5) simultaneously

for three seconds. Press the

I button until the feature

requiring adjustment is displayed:

* Settings available for adjustment on the 3-digit display

only if the W8735S1000 AquaReset Outdoor Reset

Module is installed.

**Settings available for adjustment only when the

W8735S1000 AquaReset Outdoor Reset Kit is NOT

installed.

Then press the

UP and/or DOWN buttons to move the set

point to the desired value, to change between °F and °C,

or to enable (On) or disable (Off) the External Low Limit.

After 60 seconds without any button inputs, the control will

automatically return to the

RUN mode.

Display

In the

RUN mode, the Aquastat will flash “bt” (boiler temp)

followed by the temperature (i.e., 220), followed by °F or

°C.

To read boiler settings, press the

I key to read the

parameter of interest. For example, press

I and High Limit

(

HL) is displayed, followed by a three-digit number, i.e.,

220, followed by °F or °C. Pressing the

I button again (on

L7224 models) will display the Low Limit (

LL) followed by

a three-digit number and the corresponding degree

designator. See Display Readout, Table 4.

After approximately 60 seconds without any key presses,

the display will enter a dim display mode. To return to the

bright display mode, simply press any key.

Table 3. Adjustable Features.

Display

Definition

HL_

High Limit.

FP_

Frost Protection (ON/OFF) (L7248L only)

Hdf

High Limit Differential.

LL_

Low Limit. (L7224A, C)

Ldf

Low Limit Differential (L7224A, C)

ELL

External Low Limit (L7248L only)

duu

ZR input configured as external Domestic Hot

Water (DHW) request (ON/OFF) (L7224A,C/

L7248L)

ASC

Anti Short-Cycle Timeout (seconds); “OFF” is

disabled.

otL*

Outdoor Temperature Low (minimum)

parameter for the outdoor reset curve (°F or °C)

otH*

Outdoor Temperature High (maximum)

parameter for outdoor reset curve (°F or °C)

btL*

Boiler Temperature Low (minimum) parameter

for outdoor reset curve

bP*

Boost Period (minutes). “OFF” is displayed if

Boost is inactive

bS*

Boost step (°F or °C) shown only if Boost is

active (bP=ON)

UUS*

Warm Weather Shutdown Temperature

(°F or °C)

tPL**

Thermal Purging Limit Temperature (°F or °C),

“OFF” if disabled

tPt**

Termal Purging Time Delay (minutes), shown

only if tPL is enabled

PC

Pump Cycling (ON / OFF)

F-C

Temperature units (°F or °C)