Performance Under Rated Conditions * - Model STR13D (0-5 to 0-100 psid)

Parameter

Description

Upper Range Limit **

psid

bar

100
7

Minimum Span

psid

bar

5
0.35

Turndown Ratio

20 to 1

Zero Elevation and Suppression No limit except minimum span within –18% and +100% of URL. Specifications valid from

–5% to 100% of URL.

Accuracy

(Reference – Includes

combined effects of linearity,
hysteresis, and repeatability)

Stated accuracy does not apply

for models with 2.9 inch
diameter remote seal
diaphragms.

Accuracy includes residual error

after averaging successive
readings.

For F

OUNDATION

Fieldbus use

Digital Mode specifications. For
HART use Analog Mode
specifications.

In Analog Mode:

±0.1% of calibrated span or upper range value (URV), whichever is

greater, terminal based.
For URV below reference point (30 psi), accuracy equals:

±0.05 + 0.05

(

)

30 psi

span psi

or ±0.05 + 0.05

(

)

2 bar

span bar in % of span

In Digital Mode:

±0.075% of calibrated span or upper range value (URV), whichever is

greater, terminal based.
For URV below reference point (30 psi), accuracy equals:

±0.025 + 0.05

(

)

30 psi

span psi

or ±0.025 + 0.05

(

)

2 bar

span bar in % of span

Combined Zero and Span

Temperature Effect per 28°C
(50°F) ***

In Analog Mode:

±0.33% of span.

For URV below reference point (60 psi), effect equals:

±0.05 + 0.2

60 psi

span psi

or ±0.05 + 0.28

4 bar

span bar

In % span

±0.05 + 0.2

60 psi

span psi

or ±0.05 + 0.28

4 bar

span bar

In % span

In Digital Mode:

±0.305% of span.

For URV below reference point (60 psi), effect equals:

±0.025 + 0.25

60 psi

span psi

or ±0.025 + 0.28

4 bar

span bar

In % span

±0.025 + 0.25

60 psi

span psi

or ±0.025 + 0.28

4 bar

span bar

In % span

* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.

** Transmitter URL limit or maximum seal pressure rating, whichever is lower.

*** Specification applies to transmitters with 2 seals only. Apply 1.5 times factor to temperature effect for capillary lengths greater than 10
feet.