Voltage at timer terminals – Honeywell 191108AJ User Manual

Page 21

Advertising
background image

21

69-0643—1

Voltage At Timer Terminals

AC Voltages at
C-C Terminals

Check

Action

0 Vac.

— System power off.

— Restore power.

— Short in timer power supply wiring.

— Replace wiring.

— Limit switch contacts stuck open.

— Free or replace limit switch.

— Transformer supplying power is

— Replace transformer.

burned out.

Up to 15 Vac.

— System transformer used to power

— Use additional (separate)

the timer is inadequate.

transformer.

— Additional (separate) transformer

— Install transformer with proper

used to power the timer has

secondary voltage.

inadequate voltage.

15 to 30 Vac.

— Spring fingers on thermostat not

— Rebend spring fingers to a 45

making proper contact with subbase

degree angle to assure proper

terminals.

contact.

— Timer has failed.

— Replace thermostat.

Advertising