System on indicator
(flame=heat,
snowflake=cool) is
displayed, but no
warm or cool air is
coming from the
registers.

Fan operation set for 0 (con-
ventional heat) when it should
be set for 1 (electric heat).

Enter Installer Setup number 2 and reconfigure the fan
operation.

Conventional heating equipment
turns on the fan when the
furnace has warmed up to a
setpoint.

Wait a minute after seeing the on indicator and then check the
registers.

Heating or cooling equipment is
not operating.

Verify operation of heating or cooling equipment in self-test.

Outdoor tempera-
ture not displayed

a

Option not activated.

Enter Installer Setup number 24 and set to 1. Thermostat must
have OT terminals and a C7089B1000 Sensor installed.

Outdoor
temperature
display is incorrect

a

Outdoor sensor is connected
incorrectly.

Refer to C7089B1000 Installation Instructions and check wiring
between the thermostat and sensor.

Wrong sensor.

Replace sensor with C7089B1000 Sensor.

a

Select models.

Table 6. Troubleshooting Guide. (Continued)

Symptom

Possible Cause

Action