TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS

62-2016—01

16

Pwr del

Power-up delay
Default value = 10 seconds

On initial power up of the thermostat (each time 24 Vac power
supply is removed and re-applied) there is a delay before any
operation is authorized (fan, cooling or heating). This can be used
to sequence start up multiple units/thermostat in one location.
10 to 120 seconds

Frost pr

Frost protection enabled
Default value = Off
On heat pump models the
system mode will be forced to
EMERGENCY mode if frost
protection is activated

Off: no room frost protection
On: room frost protection enabled in all system mode at: 42 F
(5.6 C)
Frost protection is enabled even in system Off mode
Off or On

Heat max

Maximum heating setpoint limit
Default value = 90 F (32 C)

Maximum occupied and unoccupied heating setpoint adjustment.
Heating setpoint range is: 40 F to 90 F (4.5 to 32.0 C)

Cool min

Minimum cooling setpoint limit
Default value = 54 F (12 C)

Minimum occupied and unoccupied cooling setpoint adjustment.
Cooling setpoint range is: 54 F to 100 F (12.0 to 37.5 C)

Pband

Proportional Band setting
Default value 2 = 2.0 F (0.6 C)

Adjust the proportional band used by the thermostat PI control loop.

CAUTION

Note that the default value of 2.0 F (1.1 C) gives
satisfactory operation in most normal installation cases. The
use of a superior proportional band different than the factory
one is normally warranted in applications where the
thermostat location is problematic and leads to unwanted
cycling of the unit. A typical example is a wall mounted unit
where the thermostat is installed between the return and
supply air feeds and is directly influenced by the supply air
stream of the unit.

Table 14. Configuration Parameters for all models (Continued)

Configuration

parameters

Significance Default value

Adjustments

Table 15. Keypad Lock Out Levels

Level

Resume/
Override

scheduling

Permanent

Occupied

and

Unoccupied

Setpoints

Temporary

setpoints

using arrows

System

mode

setting

Fan mode

setting

Schedules

setting

Clock

setting

Permanent

hold

Resume
sched Y/N

RoomTemp
set Y/N

Up key ( )

Down key ( )

Sys mode
set Y/N

Fan mode
set Y/N

Schedule
set Y/N

Clock
set Y/N

Schedule
hold Y/N

0

Yes access Yes access

Yes access

Yes access Yes access Yes access Yes access Yes access

1

Yes access No access

Yes access

No access No access No access Yes access No access

2

No access

No access

No access

No access No access No access Yes access No access

Value F scale Pband

C scale Pband

2

2 F

1.1 C

3

3 F

1.7 C

4

4 F

2.2 C

5

5 F

2.8 C

6

6 F

3.3 C

7

7 F

3.9 C

8

8 F

4.4 C