TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS

17

62-2016—01

Anticycle

Minimum on/off operation time for
stages
Default value = 2 minutes

Minimum on/off operation time of cooling and heating stages.

CAUTION

Anti-short cycling can be set to 0 minutes for equipment that
has an anti cycling timer. Do not set to 0 unless the
equipment has internal anti-cycling timer or damage to
equipment can occur.

0, 1, 2, 3, 4 and 5 minutes

Heat cph

Heating stages cycles per hour
Default value = 4 cph
For multi stage models, heat cph
applies to W1 and W2
For heat pump models, heat cph
applies to W1 only
(Emergency heat)

Will set the maximum number of heating stage cycles per hour
under normal control operation. It represents the maximum number
of cycles that the equipment will turn ON and OFF in one hour.
Note that a higher cph will represent a higher accuracy of control at
the expense of wearing mechanical components faster.
3, 4, 5, 6,7 and 8 cph

Cool cph

Cooling stages cycles per hour
Default value = 4 cph
For multi stage models, cool cph
applies to Y1 and Y2
For heat pump models, cool cph
applies to Y1 and Y2 in cooling
and heating independently of the
reversing valve position

Will set the maximum number of cooling stage cycles per hour
under normal control operation. It represents the maximum number
of cycles that the equipment will turned on and off in one hour.
Note that a higher cph will represent a higher accuracy of control at
the expense of wearing mechanical components faster.
3 or 4 cph

Deadband

Minimum deadband
Default value = 2.0 F (1.1 C)

Minimum deadband value between the heating and cooling
setpoints. If modified, it will be applied only when any of the
setpoints are modified.
2, 3 or 4 F (1.0 to 2.0 C)

Fan cont

Fan control
Default value = On
For multi stage models, fan
control applies to W1 and W2
For heat pump models, fan
control applies to W1 only
(Emergency heat)

Fan control in heating mode.
When selecting On; the thermostat in all cases will always control
the fan (terminal G).
Valid for On or Auto fan mode
When selecting Off; the fan (terminal G), when heating stages
(terminals W1 and W2) are solicited, will not be energized. The fan
in this case will be controlled by the equipment fan limit control.
Valid only for Auto fan mode. On fan mode will leave the fan always
on.
On or Off

Fan del

Fan delay
Default value = Off

Fan delay extends fan operation by 60 seconds after the call for
heating or cooling ends.
Valid only for Auto fan mode. On fan mode will leave the fan always
on.
Off or On

ToccTime

Temporary occupancy time
Default value = 3 hours

Temporary occupancy time with occupied mode setpoints when
override function is enabled
When the thermostat is in unoccupied mode, function is enabled
with either the menu or DI1 or DI2 configured as remote override
input.
0,1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11 and 12 hours

Cal RS

Room air temperature sensor
calibration
Default value = 0.0 F or C

Offset that can be added/subtracted to actual displayed room
temperature
± 5.0 F (± 2.5 C)

Cal OS

Outside air temperature sensor
calibration
Default value = 0.0 F or C

Offset that can be added/subtracted to actual displayed outside air
temperature
± 5.0 F (± 2.5 C)

H stage

Number of heating stages.
Applicable to 2 stage models only
Default value = 2 stages
For heat pump models, H stage
is limited to 1 stage only
(W1 – Aux. Heat).

Will revert the operation of 2 stages thermostat to single stage
operation only when the second heating step is not needed.
1 or 2 stages

Table 14. Configuration Parameters for all models (Continued)

Configuration

parameters

Significance Default value

Adjustments