TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS

62-2016—01

6

Detailed Wiring Diagrams for Selected Models

Fig. 6. TB7656B5x00(x) 2 Heat/2 Cool/Economizer/Programmable

Fig. 7. TB7652H5x00(x) Heat pump/Programmable

Sensor Wiring for all Thermostat Models

Remote mount outdoor temperature sensors must be10 Kohm NTC @ 77 F.

Remote sensors can be used for:
• Various averaging combinations (3 thermistors with 2 dip switches are provided with each sensor)
• Optional occupancy led
• Optional override key

Table 2. Temperature vs. Resistance for 10 Kohm NTC thermistor (R

25°C

= 10KW±3%, B

25/85°C

= 3975K±1.5%)

ºF

ºC

Kohm

ºF

ºC

Kohm

ºF

ºC

Kohm

ºF

ºC

Kohm

ºF

ºC

Kohm

-40 -40 324.3197

-4

-20 94.5149

32

0

32.1910

68

20

12.4601

104 40

5.3467

-31 -35 234.4009

5

-15 71.2430

41

5

25.1119

77

25

10.0000

113 45

4.3881

-22 -30 171.3474

14

-10 54.1988

50

10

19.7390

86

30

8.0694

122 50

3.6202

-13 -25 126.6109

23

-5

41.5956

59

15

15.6286

95

35

6.5499

131 55

3.0016

Y2

Y1

G

RC

C

RH

W1

JUMPER

J1

COOL

STAGE 2

COOL

STAGE 1

FAN

HEAT

STAGE 1

HEAT

STAGE 2

0-10 VDC

24V

COM

AUXILIARY

OUTPUT

W2

EC

AU

DI1

DI2

DIGITAL INPUT #1

DIGITAL INPUT #2

RS

Scom

OS

MS

REMOTE

MIXED AIR

SENSOR

REMOTE

OUTDOOR

SENSOR

REMOTE

ROOM

SENSOR

FIELD CONTACTS

THERMOSTAT

INTERNAL WIRING

SYSTEM WIRING

M16929

24 VAC

T1

ECONOMIZER

ACTUATOR

Y2

Y1

G

RC

C

RH

W1

JUMPER

J1

COMPRESSOR

STAGE 2

COMPRESSOR

STAGE 1

FAN

AUXILIARY

HEAT

REVERSING

VALVE

AUXILIARY

OUTPUT

O/B

AU

DI1

DI2

DIGITAL INPUT #1

DIGITAL INPUT #2

RS

Scom

OS

MS

REMOTE

MIXED AIR

SENSOR

REMOTE

OUTDOOR

SENSOR

REMOTE

ROOM

SENSOR

THERMOSTAT INTERNAL WIRING

SYSTEM WIRING

24 VAC

T1

FIELD CONTACTS

M16930