TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS

62-2016—01

22

Table 19. Troubleshooting Guide for Heat Pump Models

Symptom

Possible Cause

Corrective Action

Auxiliary heat does not
operate

Wrong mode selected

Select emergency heat mode

Thermostat in Unoccupied
mode

Select Occupied Hold in Schedule hold or Override to force
the thermostat Occupied heating setpoint

Anti-cycle delay active

Wait, the anti-cycling period will end and the equipment will
start

Heating setpoint is satisfied

Raise the Heating setpoint

High Balance point attained

Mode is locked out based on outside air temperature
Change configuration parameter High BP to value 90 F (32 C)
to by-pass lockout

Heating lockout attained

Mode is locked out based on outside air temperature
Change configuration parameter H Lock to value 120 F (49 C)
to by-pass lockout

Wiring error

Start the Fan by forcing the Fan ON mode
Put a jumper across terminals RH and W1. The heating
should come ON. If it does not, verify wiring and check if a
jumper is required between RC and RH

Heat pump does not
operate in heating mode

Wrong mode selected

Select heating mode

Thermostat in Unoccupied
mode

Select Occupied Hold in Schedule hold or Override to force
the thermostat Occupied heating setpoint

Anti-cycle delay active

Wait, the anti-cycling period will end and the equipment will
start

Heating setpoint is satisfied

Raise the Heating setpoint

Low Balance point attained

Mode is locked out based on outside air temperature
Change configuration parameter Low BP to value -12 F
(-24 C) to by-pass lockout

Heating lockout attained

Mode is locked out based on outside air temperature
Change configuration parameter H Lock to value 120 F (49 C)
to by-pass lockout

Wiring error

Start the Fan by forcing the Fan ON mode
Put a jumper across terminals RH and W1. The heating
should come ON. If it does not, verify wiring and check if a
jumper is required between RC and RH

Wrong reversing valve
configuration

Wrong selection of parameter Re Valve
Select O will energize the valve in cooling operation. Valve is
normally heat.
Select B will energize the valve in heating operation. Valve is
normally cool.