Specifications – Honeywell SERIES COMMUNICATING TB7600 User Manual

Page 23

Advertising
background image

TB7600 SERIES COMMUNICATING RTU/HEAT PUMP THERMOSTATS

23

62-2016—01

SPECIFICATIONS

Network Protocol: Models available in BACnet MS/TP or ZigBee wireless mesh

WEBs-AX Controllers: Compatible with WEB-2xx, WEB-6xx, and WEB-7xx

Platform:

WEB-2xx and WEB-6xx - WEBStation-AX 3.0 or later
WEB-7xx - WEBStation-AX 3.5 or later

Thermostat power requirements:

19-30 Vac 50 or 60 Hz; 2 VA (RC and C) Class 2
RC to RH jumper 2.0 Amps 48 VA maximum

Operating conditions:

32 F to 122 F (0 C to 50 C)
0% to 95% R.H. non-condensing

Storage conditions:

-22 F to 122 F (-30 C to 50 C)
0% to 95% R.H. non-condensing

Sensor: 10 K NTC thermistor onboard

Resolution: ± 0.2 F (± 0.1 C)

Control accuracy: ± 0.9 F (± 0.5 C) @ 70 F (21 C) typical calibrated

Occupied and unoccupied setpoint range cooling: 54 F to 100 F (12.0 to 37.5 C)

Occupied and unoccupied setpoint range heating: 40 F to 90 F (4.5 C to 32 C)

Room and outdoor air temperature range: -40 F to 122 F (-40 C to 50 C)

Proportional band for room temperature control: Factory set, heating and cooling at 2.0 F (1.1 C)

Digital inputs: Relay dry contact only across C terminal to DI1 or DI2

Contact output rating:

Each relay output: (Y1, Y2, G, W1, W2 and AU)
30 Vac, 1 Amp maximum
30 Vac, 3 Amp in-rush

Economizer analog output rating: 0 to 10 Vdc into 2K

Ω

resistance min.

Economizer analog output accuracy: ± 3% typical

Wire gauge: 18 gauge maximum, 22 gauge recommended

Dimensions: see Fig. 13.

Approximate shipping weight: 0.75 lb (0.34 kg)

62-2016.fm Page 23 Thursday, April 14, 2011 1:40 PM