Table 8.2 b. using offsets/returns – Hearth and Home Technologies Wood Burning Fireplace HST-42D User Manual

Page 26

Advertising
background image

26

Table 8.2

B. Using Offsets/Returns

• Use an offset/return to bypass overhead obstructions.
• An offset and return can be used as a single entity or separated by chimney section(s).

WARNING! Risk of Fire! DO NOT use offset/returns greater than 30°. Chimney draft will be restricted and could cause
overheating and fi re.

• Measure the shift needed to avoid the overhead obstruction. Refer to dimension A in Figure 8.3.
• Find the appropriate A dimension listed in Table 8.2.
• The B dimension coinciding with the A dimension measurement in Table 8.2 represents the required vertical clearance

needed to complete the offset/return.

• Read across the chart to fi nd the number of chimney sections/model numbers needed between the offset and return.

A

B

1-1/4 in. (32 mm)

OVERLAP

Figure 8.3 Chimney Offset/Return

Heat & Glo • HST-42D • 27177 • Rev AB • 11/08

15-degree

SL306 SL312 SL318 SL324 SL336 SL348

30-degree

A

Offset

B

Height

A

Offset

B

Height

in.

mm

in.

mm

in.

mm

in.

mm

1-5/8

41

13-3/8 340

-

-

-

-

-

-

3-5/8

92

15-1/2

394

2-7/8

73

17-3/4 451

1

-

-

-

-

-

5-1/2

140

18-5/8

473

4-1/8

102

22-3/8 568

2

-

-

-

-

-

7-1/4

184

21-3/4

552

4-1/2

114

23-5/8 600

-

1

-

-

-

-

8-1/2

216

23-3/4

603

5-3/4

146

28-1/4 718

1

1

-

-

-

-

10-1/4

260

27

686

6

152

29-3/8 746

-

-

1

-

-

-

11-1/2

292

29

737

7-1/4

184

34

864

-

2

-

-

-

-

13-1/4

337

32-1/8

816

7-3/4

197

36-1/8 918

-

-

-

1

-

-

14-1/2

368

34-1/8

867

8-3/4

222

39-3/4 1010

1

-

-

1

-

-

16-1/4

413

37-3/8

949

10-3/8

264

45-5/8 1159

-

-

2

-

-

-

19-1/4

489

42-1/2

1080

10-5/8

270

46-3/4 1187

-

-

-

-

1

-

20-1/2

521

44-5/8

1133

11-7/8

302

51-3/8 1305

1

-

-

-

1

-

22-1/4

565

47-3/4

1213

13-1/2 243

57-1/4 1454

-

-

-

2

-

-

25-1/4

641

52-7/8

1343

13-3/4 349

58-3/8 1483

-

-

-

-

-

1

26-1/2

673

55

1397

15

381

63

1600

1

-

-

-

-

1

28-1/4

718

58-1/8

1476

16-1/2 419

68-3/4 1746

-

1

-

-

-

1

31-1/4

794

63-1/4

1607

18

457

74-5/8 1895

-

-

1

-

-

1

34-1/4

870

68-1/2

1740

19-5/8 498

80-3/8 2042

-

-

-

1

-

1

37-1/4

946

73-3/4

1873

20-5/8 524

84-1/8 2137

1

-

-

1

-

1

39-1/8

994

76-7/8

1953

22-3/4 578

91-7/8 2334

-

-

-

-

1

1

43-1/4

1099

84-1/8

2137

24

610

96-1/2 2451

1

-

-

-

1

1

45-1/8

1146

87-1/4

2216

25-7/8 657

103-1/2 2629

-

-

-

-

-

2

49-1/4

1251

94-1/2

2400

Proper assembly of air-cooled chimney parts result in an overlap at chimney joints of 1-1/4 in. (32 mm). Effective length is built
into this chart.

Example:

Your “A” dimension from Figure 8.3 is 14 1/2 in. (368
mm). Using Table 8.2 the dimension closest to, but
not less than 14 1/2 in. (368 mm) is 14 1/2 in. (368
mm) using a 30° offset/return.

You determine from the table that you need 34 1/8 in.
(867 mm) (Dimension “B”) between the offset and
return.

The chimney component that best fi ts your applica-
tion is one SL324.