TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

11

62-0221—05

0240

CPH for first stage
conventional heat

5

1-12

Only shown for conventional system with heat
stages (ISU 0170).
Selection in this stage changes default CPH of
second stage heat.

0250

CPH for second
stage conventional
heat

9

1-12

Only shown for conventional system with at least
two stages conventional heat or 2H/1C heat pump
(ISU 0170).

0260

CPH for third Stage
Heat

9

1-12

Only shown for 3H/2C heat pump system (ISU
0170).

0270

CPH for Auxiliary
Heat

9

1-12

Only shown for multi-stage heat pump system with
more heat than cool stages (ISU 0170).

0280

Continuous
Backlight

0

0—No
1—Yes

Always shown. If AC power not present the option
is overridden and normal backlight operation
occurs.

0300

Changeover

1

0—Manual
1—Auto

Only shown for system with both heat and cool
stages (ISU 0170).

0310

Deadband

3°F
(2°C)

2 (1.5)—2°F (1.5°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)

Only shown for Auto Changeover system (ISU
0300).

0320

Temperature
Indication Scale

0

0—°F
1—°C

0330

Daylight Saving

2

0—Disabled
1—Enabled (US 1987)
2—Enable (US 2007)
3—Enabled (Europe)

0340

Remote
Temperature
Sensor

0

0—None
1—Outdoor for Display
2—Outdoor for Control
3—Remote 10K Indoor
4—Remote 20K Indoor

Averaging would not include on-board sensor. It is
accomplished by series/parallel combinations.
2 applies only to Heat Pump applications (allowing
compressor lockout while displaying temperature).

0350

Heat Pump
Compressor
Lockout

0

0—None
15(-9.5)—15°F (-9.5°C)
20(-6.5)—20°F (-6.5°C)
25(-4.0)—25°F (-4.0°C)
30(-1.0)—30°F (-1.0°C)
35(1.5)—35°F (1.5°C)
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)

Only shown for heat pump systems with more heat
stages than cool (ISU 0170) and remote outdoor
control sensor (ISU 0340 is 2).
Must enforce a dead band between this and
Auxiliary Lockout.

0360

Heat Pump
Auxiliary Lockout

0

0—None
40(4.5)—40°F (4.5°C)
45(7.0)—45°F (7.0°C)
50(10.0)—50°F (10.0°C)
55(13.0)—55°F (13.0°C)
60(15.5)—60°F (15.5°C)

Only shown for heat pump systems with more heat
stages than cool (ISU 0170) and remote outdoor
control sensor (ISU 0340 at 2).
Must enforce a dead band between this and Heat
Pump Compressor Lockout.

0535

Temporary
Occupied Duration
Limit

3

0—no duration
1—one hour
2—two hours
3—three hours
4—four hours

0 means no limit.

0540

Number of Periods 4

2—2 Periods
4—4 Periods

Does not appear if Non-programmable is chosen
(ISU 0160).
Applies to all days of the week.

0580

Minimum
Compressor Off
Time

5

0—Off
2—2 minutes
3—3 minutes
4—4 minutes
5—5 minutes

Only shown if system has cool stages (ISU 0170).