TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

62-0221—05

12

NOTE: Press the Done key to exit the Installer System Test.

0600

Heat Temperature
Range Stops

90

40 to 90°F (4 to 32°C)

Only shown if system has heat stages (ISU 0170).

0610

Cool Temperature
Range Stops

50

50 to 99°F (10 to 37°C)

Only shown if system has cool stages (ISU 0170).

0640

Clock Format

12

12—12 Hour
24—24 Hour

0650

Extended Fan-on
time Heat

0

0—Off
90—90 seconds

Not displayed with cool-only systems (ISU 0170)
or with fan set to system control (ISU 0180 at 0).

0660

Extended Fan-on
time Cool

0

0—Off
40—40 seconds

Only shown for systems with cool stages (see ISU
0170).

0670

Keypad Lockout

0

0—Unlocked
1—Partial Lockout 1
2—Partial Lockout 2
3—Fully Locked

Unlocked: All functions accessible.
Partial 1: Locks all but Holiday, Override, and Up/
Down.
Partial 2: Locks all but Holiday and Override.
Full: Entire interface locked/non-functional.

0680

Temperature
Control Heat

2

1—Less Aggressive
2—Standard
3—More Aggressive

Only shown if system has heat stages (ISU 0170).
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)

0685

Recovery Heat
Ramp Rate

5

0-20°F/hour

Only shown if system has heat stages (ISU 0170).
0 disables ramped recovery (step setpoint change
at period start time).

0690

Temperature
Control Cool

2

1—Less Aggressive
2—Standard
3—More Aggressive

Only shown if system has cool stages (ISU 0170).
Only integral gains affected. Affects control
operation in all control regimes (not just recovery
or setpoint change).
More Aggressive stops signal prior to reaching the
setpoint. (For use with oversized equipment.)

0695

Recovery Cool
Ramp Rate

3

0-20°F/hour

Only shown if system has cool stages (ISU 0170).
0 disables ramped recovery (step setpoint change
at period start time).

0700

Temperature
Display Offset

0

-3 (-1.5)— -3°F (-1.5°C)
-2 (-1.0)— -2°F (-1.0°C)
-1 (-0.5)— -1°F (-0.5°C)
0 (0.0)—0°F (0.0°C)
1 (0.5)—1°F (0.5°C)
2 (1.0)— 2°F (1.0°C)
3 (1.5)—3°F (1.5°C)

This offset applies to both the control temperature
and to the display temperature for indoor sensor
(and remote indoor sensor).

0710

Restore Factory
Defaults

0

0—No
1—Yes

Resets all ISU parameters to default values and
resets the schedule to default (see Table 5).
Retains only calendar settings and time.

INSTALLER TESTS

Test 1

Installer Test
Cool

0

0—Off
1—Cool Stage 1
2—Cool Stage 2

Test 2

Installer Test
Fan

0

0—Off
1—Fan On

Test 3

Installer Test
Heat

0

0—Off
1—Heat Stage 1
2—Heat Stage 1 and 2
3—Heat Stage 1,2 and 3

Test 4

Installer Test
Auxiliary Heat

0

0—Auxiliary Heat Off
1—Auxiliary Heat On

Test 8

Installer Test
TOD/Economizer

0

0—TOD/Economizer Off
1—TOD/Economizer On

Table 4. Installer Setup Menu. (Continued)

Installer

Setup

Number

Installer Setup

Name

Default
Setting

All Settings

Notes