Power the thermostat, Wiring 24 vac common, Installing batteries – Honeywell COMMERCIALPRO TB7220U User Manual

Page 8: Mount thermostat to wallplate

Advertising
background image

TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

62-0221—05

8

POWER THE THERMOSTAT

You can choose from three methods to power the
thermostat:
• Batteries only (AA alkaline).
• 24 Vac direct connection only.
• 24 Vac direct connection with battery backup (AA

alkaline).

Wiring 24 Vac Common

• Single-Transformer System—Connect the common

side of the transformer to the C screw terminal of the
thermostat wallplate. Leave the metal jumper wire in
place between RC and R.

• Two-Transformer System—Connect the common side

of the cooling transformer to the C screw terminal of
the thermostat wallplate. Remove the metal jumper
wire between RC and R.

Installing Batteries

1. Install two AA alkaline batteries on the back of the

thermostat as marked. See Fig. 21.

Fig. 21. Installing batteries.

2. Locate and remove the tab labeled Remove. See

Fig. 22.

IMPORTANT

This tab must be removed in order to set the
real-time clock.

Fig. 22. Remove tab labeled REMOVE from thermostat

back.

Mount Thermostat to Wallplate

1. Align the terminal screw blocks with the pins on the

back of the thermostat.

2. Push the thermostat straight onto the wallplate until

it snaps into place. See Fig. 23.

Fig. 23. Mount thermostat to wallplate.

M22259

BACK OF THERMOSTAT

BATTERY HOLDER

BATTERIES (2)

REMOVE

TAB

REMOVE DURING

INSTALLATION

M22260

REMOVE DURING

INSTALLATION

WALL

M23024

Advertising