TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

5

62-0221—05

Fig. 11. Typical hookup of single transformer

multistage system (up to 2H/2C).

Fig. 12. Typical hookup of dual transformer multistage

system (up to 2H/2C).

M23016

HEAT RELAY 2

OUTDOOR/INDOOR

TEMPERATURE

SENSOR

FAN RELAY

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.

FACTORY INSTALLED JUMPER.

WHEN USING BATTERIES, THE 24V COMMON CONNECTION

IS OPTIONAL.

1

3

2

3

COOL RELAY 1

HEAT RELAY 1

COOL RELAY 2

L1

(HOT)

L2

1

24 VAC

ECONOMIZER

C
G
Y
W
RC
R

W2

Y2

A

S1
S2

2

M23017

HEAT RELAY 2

OUTDOOR/INDOOR

TEMPERATURE

SENSOR

FAN RELAY

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.

REMOVE FACTORY INSTALLED JUMPER.

WHEN USING BATTERIES, THE 24V COMMON CONNECTION

IS OPTIONAL. WHEN USED, THE COMMON MUST CONNECT

TO THE COOLING TRANSFORMER SECONDARY.

1

3

2

3

COOL RELAY 1

HEAT RELAY 1

COOL RELAY 2

L1

(HOT)

L2

1

24 VAC

L1

(HOT)

L2

1

24 VAC

ECONOMIZER

C
G
Y
W
RC
R

W2

Y2

A

S1
S2

2

COOLING

TRANSFORMER

HEATING

TRANSFORMER