TB7220U COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

13

62-0221—05

OPERATION

System Settings

HeatThermostat controls the heating system.
OffBoth heating and cooling systems are off.
CoolThermostat controls the cooling system.
AutoThermostat automatically changes between heat
and cool operation, depending on indoor temperature.

Fan Settings

Auto Fan runs only when heating/cooling system is on.
OnFan runs continuously.

Table 5 shows default program settings. See Owner’s
Guide for complete instructions to change the program.

Table 5. Default Program Settings.

Minimum-Off Timer
(Compressor Protection)

The thermostat has an adjustable Minimum-Off Timer that
can be set from zero to five minutes (Factory Setting—five
minutes). The Minimum-Off Timer can be bypassed
through the Installer System Test or it can be bypassed
permanently by setting the Minimum-Off Timer to 0
minutes in the Installer Setup. The Minimum-Off Timer is
activated after the compressor turns off:
— If the thermostat is system powered (common wire),

the Minimum-Off Timer is also activated upon initial
startup and after power interruptions.

— If there is a call for cooling or heating during the

Minimum-Off Time, the thermostat displays “Wait.”

— When the Minimum Off Timer expires, “Cool On” or

“Heat On” (heat pumps only)” appears solidly in the
display and the compressor and fan turn on.

Outdoor or Indoor Temperature
Sensor

Allow outdoor or indoor temperature sensor to absorb the
air for a minimum of five minutes before taking a reading.
See the Sensor instructions for more information.

Economizer/TOD Logic (Table 6)

Table 6. Operation of Terminal A.

Heat Pump Temperature Lockouts

Dual Fuel Heat Pump and Outdoor
Sensor

In this operation, there is no external fossil fuel kit (dual
fuel kit) installed; the thermostat controls this function:

1. Choose correct heat pump application in Installer

Setup Number 0170.

2. Choose Outdoor Temperature Sensor for Heat

Pump Temperature Lockouts Option in Installer
Setup Number 0340.

3. Choose appropriate Balance Point Temperature

in Installer Setup Number 0350.

OPERATION IN HEAT MODE ABOVE BALANCE
POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is above the selected
Balance Point Temperature (ISU 0350), only the
compressor operates and the fan (G terminal) energizes
when the thermostat calls for heat.

OPERATION IN HEAT MODE BELOW BALANCE
POINT (OUTDOOR TEMPERATURE)
When the outdoor temperature is below the selected
Balance Point Temperature (ISU 0350), only the Fossil
Fuel (auxiliary heat) operates and the fan (G terminal)
does not energize when the thermostat calls for heat.

Heat Pump with Auxiliary (Backup) Heat
and Outdoor Temperature Sensor

1. Choose correct heat pump application in Installer

Setup Number 0170.

2. Choose Outdoor Temperature Sensor for

Control Option in Installer Setup Number 0340.

3. Choose Compressor Lockout Temperature in

Installer Setup Number 0350.

4. Choose Auxiliary Lockout Temperature in

Installer Setup Number 0360.

NOTE: There is a 5°F deadband between Compressor

and Auxiliary Heat lockout temperatures.

Operation in Heat Mode

When the outdoor temperature is:
— Below the Compressor Lockout Temperature, only the

Auxiliary Heat operates.

— Above the Auxiliary Lockout Temperature, only the

Compressor operates. See Fig. 31.

— Between the two temperatures, both the Compressor

and Auxiliary Heat operate.

Fig. 25. Heat Pump Operation with Lockout

Temperatures Set.

Schedule

Period

Time

Setpoints

Fan

Setting

Heat

Cool

Occ1

8:00am

70°F
(21°C)

75°F
(25.5°C)

On

Unocc1

10:00pm

55°F
(10°C)

85°F
(24°C)

Auto

Occ2

1:00pm

70°F
(21°C)

75°F
(25.5°C)

On

Unocc2

12:00pm
(Noon)

55°F
(10°C)

85°F
(24°C)

Auto

Effective

Occupancy

Call for

Cool

Terminal A

Economizer

TOD

Occupied

Energized

Energized

Unoccupied Yes

Energized

De-energized

No

De-energized

De-energized

Override

Energized

Energized

35

M19950

COMPRESSOR

LOCKOUT

TEMPERATURE

AUXILIARY

LOCKOUT

TEMPERATURE

COMPRESSOR ONLY

BOTH COMPRESSOR AND

AUXILIARY HEAT

AUXILIARY ONLY

50

OUTDOOR TEMPERATURE