Installer setup, Caution – Honeywell Chronotherm IV T8600D User Manual

Page 5

Advertising
background image

T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS

5

69-1409—1

INSTALLER SETUP

NOTE: For most applications, the thermostat factory

settings will not require changing. Review the
factory settings in Table 2 and if no changes are
necessary, go to the Installer Self-Test section.

The Installer Setup is used to customize the thermostat
to specific systems. Some of the options include
temperature display, system changeover, and outdoor
temperature display. Installer Setup numbers are listed in
Table 3. The table includes all the configuration options
and the factory settings for the T8600.

A combination of key presses is required to use the
Installer Setup feature:
— To enter the Installer Setup, press and hold the

information i key with the increase and
decrease keys until the first number is displayed.
All display segments appear for approximately three
seconds before the number is displayed. See Fig. 10
and 11.

— To advance to the next Installer Setup, press the

Time

∆ key.

— To change a setting, use the increase or

decrease key.

— To scroll the Installer Setup numbers backward, press

the Time

∇ key.

— To exit the Installer Setup, press Run Program.

Fig. 10. Display of all LCD segments.

Fig. 11. Display of Installer Setup number and

setting.

CAUTION

Electric Heat System Configuration Hazard.
Can cause equipment damage.
Configure electrical heat system to 1 in Installer
Setup number 2 to prevent system running
without fan.

IMPORTANT

Only configurable numbers are shown on the
device. Example: If thermostat does not have a
System key, Installer Setup Number 12 will not
be displayed. Review Table 3 factory settings
and mark any desired changes in the Actual
Setting column. When Installer Setup is com-
plete, review the settings to confirm that they
match the system.

Table 2. Default Program Settings.

Period

Time

Heat

Setpoint

Cool

Setpoint

Fan

Setting

Wake

6:00 AM

70°F

(21°C)

78°F

(25.5°C)

Auto

Leave

8:00 AM

62°F

(16.5°C)

85°F

(29.5°C)

Auto

Return

6:00 PM

70°F

(21°C)

78°F

(25.5°C)

Auto

Sleep

10:00 PM

62°F

(16.5°C)

82°F

(28°C)

Auto

M14559

Aux Ht

Set Day/Time

Set Program

Mon
Wake Leave Return

Sleep

Outdoor

Room

Filter

Wait

System

Fan

Em Heat

On

Auto

Off

Cool

Auto

AM

PM

Hold for

Heat

Cool

Repl Batt

Recovery

DST

Tue Wed Thu Fri Sat Sun

Days

Temporary Setting

Em Ht

M14618

INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2 OF TABLE 3)

FACTORY SETTING OR OTHER
CHOICE DISPLAY (COLUMN 3
OR 5 OF TABLE 3)

Advertising