Installer system test, Caution – Honeywell Chronotherm IV T8600D User Manual

Page 9

Advertising
background image

T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS

9

69-1409—1

NOTE: You can view the number of days remaining at

any time by pressing the i key three or four
times. If more than one timer is active, all active
timers show sequentially when pressing the i
key several times.

INSTALLER SYSTEM TEST

Use the Installer System Test to check the thermostat
operation. Refer to Table 4 for a list of the available
system tests.

CAUTION

Equipment Damage Hazard.
Minimum compressor off-time is bypassed
during Installer System Test.
Avoid cycling compressor quickly.

To start the system test:
Press and hold the increase and decrease keys at
the same time until 10 appears. All segments of the
display are displayed before the 10 appears. See Fig. 12
and 13.

Fig. 12. LCD segments display.

Fig. 13. Test number display.

Refer to Table 5 for the directions and results of the
specific tests.

NOTE: Press Time

∆ to advance to the next test and

Time

∇ to go back to the previous test. Press

Run Program to exit the system test

Table 4. Tests Available In Installer System Test.

Test

Number

System Test Description

10-19

Heating equipment can be turned on and
off.

30-39

Cooling equipment can be turned on and
off.

40-49

Fan equipment can be turned on and off.

60 0 to
60 19

Keyboard keys test.

70-79

Thermostat information, including date
code and software versions, is displayed.

M14559

Aux Ht

Set Day/Time

Set Program

Mon
Wake Leave Return

Sleep

Outdoor

Room

Filter

Wait

System

Fan

Em Heat

On

Auto

Off

Cool

Auto

AM

PM

Hold for

Heat

Cool

Repl Batt

Recovery

DST

Tue Wed Thu Fri Sat Sun

Days

Temporary Setting

Em Ht

M14612

Table 5. Installer System Test Options.

Keys to

Press

Test

Number

Description

Heating Equipment System Test

Time

10

Enter heating equipment system test.

11

Heat comes on. When Installer Setup number 2 is 1; the system fan is also energized.

10

Heat and system fan turn off.

Cooling Equipment System Test

Time

30

Change from heating to cooling equipment system test.

31

Cool and system fan come on.

30

Cool and system fan turn off.

Fan Equipment System Test

Time

40

Change from cooling to fan equipment system test.

Advertising