T8600D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS

69-1409—1

6

Table 3. Thermostat Installer Setup Options.

Select

Installer Setup

Number

(Press Time

key to

change)

Factory Setting

Other Choices

(Press or key to change)

Actual

Setting

Display

Description

Display

Description

Not used.

1

Fan
operation

a

.

2

0

Conventional
applications
where equipment
controls fan
operation in heat
mode.

1

Heat pump or electric heat
applications where
thermostat controls fan
operation in heat mode.

Not used.

3

Heating
cycle rate.

4

6

6—6 cph used
for conventional
heat.

1, 3, or
9

1—1 cph used for radiant

floor heat, gravity
system.

3—3 cph used for hot

water systems or high
efficiency furnaces.

9—9 cph used for electric

heat systems.

Not used.

5 thru 11

System
setting
adjustment

12

1

Manual
changeover

0 or 2

0—Auto changeover.
2—Auto only

Adaptive
Intelligent
Recovery™
control.

13

0

Adaptive
Intelligent
Recovery™
control is
activated (system
starts early so
setpoint is
reached by start
of program
period).

1

Conventional recovery
(system starts recovery at
programmed time).

Degree
temperature
display

14

0

Temperature is
displayed in °F

1

Temperature is displayed
in °C

Not used.

15

Clock
format.

16

0

12-hour clock
format.

1

24-hour clock format.

Not used.

17 and 18

Extended
fan operation
in heating

a

19

0

No extended fan
operation after
the call for heat
ends.

1

Fan operation is extended
90 seconds after the call
for heat ends.

Extended
fan operation
in cooling

20

0

No extended fan
operation after
the call for cool
ends.

1

Fan operation is extended
90 seconds after the call
for cool ends.

Not used.

21 thru 23