One elbow two elbows, Top vent - horizontal termination - (continued) – Heat & Glo Fireplace ST-36TRLP-IPI User Manual

Page 28

Advertising
background image

Heat & Glo • ST-36TR-IPI, PIER-36TR-IPI • 2176-900 Rev. G • 3/13

28

H

1

V

1

Figure 7.4

Figure 7.5

One Elbow

Two Elbows

INSTALLED

HORIZONTALLY

H

1

H

2

V

1

1. Top Vent - Horizontal Termination - (continued)

V

1

Minimum

H

1

Maximum

Elbow only

1-1/2 ft.

457 mm

6 in.

152 mm

2-1/2 ft.

610 mm

1 ft.

305 mm

3 ft.

914 mm

2 ft.

610 mm

6 ft

1.8 m

3 ft.

914 mm

9 ft.

2.7 m

4 ft.

1.2 m

12 ft.

3.7 m

5 ft.

1.5 m

15 ft.

4.6 m

6 ft.

1.8 m

18 ft.

5.5 m

V

1

+ H

1

= 50 ft. (15.2 m) Maximum

H

1

= 18 ft. (5.5 m) Maximum

V

1

Minimum

H

1

+ H

2

Maximum

Elbow only

6 in.

152 mm

1 ft.

305 mm

2 ft.

610 mm

2 ft.

610 mm

4 ft.

1.2 m

3 ft.

914 mm

9 ft.

2.7 m

4 ft

1.2 m

12 ft.

3.7 m

5 ft.

1.5 m

15 ft.

4.6 m

6 ft.

1.8 m

18 ft.

5.5 m

V

1

+ H

1

+ H

2

= 50 ft. (15.2 m) Maximum

H

1

+ H

2

= 18 ft. (5.5 m) Maximum