8

Heat & Glo LifeStyle Collection • Dakota 42-B/Dakota 42H-B • 4036-909 • Rev J 11/08

Fireplace Structure

Mantel

B

A

If A is:

Then B

must be at

least:

in.

6 - 36

26

mm 152 - 914

660

in. 36 or more

18

mm 914 or more

457

84 in.

(2134 mm)

minimum

height

Addi

tio

nal Structure

or Sidewall

Roof or

Overhang

12 in. (305 mm)
max. combustible
mantel depth

B. Clearances

Figure 3.3 Clearances to Mantels or Other Combustibles Above Appliance

B

D
Header height.
Use only noncombustible
material below the top of
the top standoffs.

A

C

84 in.

(2134 mm)

to ceiling

0 in.

0 in. to level

of standoffs

Combustible Object

36 in.

(914 mm)

Combustible flooring may be installed next
to the front of the appliance.

1-1/2 in. (38 mm)

Drywall

0 in.

1/2 in. (13 mm)

1-1/2 in.

(38 mm)

Upper front can be
covered with
non-combustible
material or removed
and replaced with
non-combustible
material.

Figure 3.2 Framing Dimensions

C. Mantel Projections

Framing Dimensions

A

B

C

D

in.

24-1/8

43-7/8

49

43-7/8

mm

613

1114

1245

1114

Fire Risk
• Comply with all minimum

clearances to combustibles
as specifi ed.

• Framing or finishing

material used on the
front of, or in front of, the
appliance closer than the
minimums listed, must
be constructed entirely of
noncombustible materials
(i.e., steel studs, concrete
board, etc.).

Failure to comply may cause
fi re.

WARNING