T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES

63-4365

12

Step 2. Determine Required Network
Devices

A maximum of 60 nodes can communicate on a single
LonWorks

Bus segment. Each LonWorks

Bus device

comprises one node. If more than 60 nodes are needed, a
Q7751A Router or Q7740 Repeater is necessary. In a
network with Excel 15 devices, a router allows up to 120
controller nodes per network, divided between two
LonWorks

Bus segments. A router or repeater allows up

to 120 controller nodes per network, divided between two
LonWorks

Bus segments. The router comprises two

nodes (one node on each side of the router). Router and
operator access nodes are not counted in the maximum
controller node totals. All devices are able to talk to each
other through the router.

Multiple operator terminals can be connected to the
LonWorks

Bus at the same time. Table 4 summarizes

the LonWorks

Bus segment configuration rules.

Refer to the E-Bus Wiring Guidelines, form 74-2865, for a
complete description of network topology rules and
maximum wire lengths. If longer runs are required, use a
Q7740A 2-way or Q7740B 4-way repeater to extend the
length of the LonWorks

Bus. Each network segment can

only have one repeater. If more nodes or longer distances
are required, add a router or repeater to limit bus traffic or
boost distance.

In addition, a 209541B Termination Module may be
required. Refer to the E-Bus Wiring Guidelines, form 74-
2865, and the Excel 10 FTT Termination Module
Installation Instructions form, 95-7554, or if Excel 15s are
present, see Application Step 3. Lay Out Communications
and Power Wiring in the W7760A System Engineering
Guide, form 74-2969.

Step 3. Lay Out Communications and
Power Wiring

LonWorks

®

Bus Layout

The communications LonWorks

Bus, is a 78-kilobit

network that uses transformer isolation and differential
Manchester encoding.

The Free Topology Transceiver (FTT) LonWorks

communications Bus supports a polarity insensitive, free
topology wiring scheme, refer to the E-Bus Wiring
Guidelines form, 74-2865, for a complete description of
LonWorks

network topology rules.

Fig. 6 shows a typical wiring diagram for the
T7300F/Q7300H in a LonWorks® network. Fig. 7 and 8
show wiring layouts for two doubly daisy-chained
LonWorks

Bus segments.

Table 4. LonWorks

Bus Configuration Rules and Device Node Numbers.

One LonWorks

Bus Segment

Maximum Number of Controller Nodes 60

Maximum number of Excel 10s

60 nodes (minus number of Excel 15s)

Maximum number of Excel 15s

4 nodes

Total

60 nodes maximum

Two LonWorks

Bus Segments;

with Excel 15

Controllers, more than 60 devices

Maximum Number of Controller Nodes 112, plus two

nodes for router access.

One Q7751A,B Router

2 nodes

Maximum number of Excel 15s

8 nodes

Maximum number of Excel 10 RIO devices

24 nodes

Maximum number of Excel 10s (20 per each Excel 15)

112 nodes (minus number of RIOs)

Total

122 nodes maximum

Two LonWorks

Bus Segments;

without Excel 15

Controllers, more than 60 devices

Maximum Number of Controller Nodes 120, plus two

nodes for router access.

One Q7751A,B Router

2 nodes

Maximum number of Excel 10s (60 per segment)

120 nodes

Total

122 nodes maximum