Performance specifications, Input/output summary – Honeywell Q7300H User Manual

Page 8

Advertising
background image

T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES

63-4365

8

Set Temperature

Change

Time/Temp

Set Program

Occupied

Temp

Unoccupied

Start Time

Day

System

Fan

Copy

Occupied

Start Time

Run

Program

Temporary

Occupied

Continous

Unoccupied

Set Current

Day/Time

Clear

Start Time

Unoccupied

Temp

Heat/Cool

Settings

1-3/8 (35)

6-11/16 (170)

3-3/16 (77)

1-7/8

(47)

4-1/8
(105)

1/16 (2)

7-5/16 (186)

4-5/8
(117)

1-11/16

(43)

7/8

(22)

M16086A

Fig. 3. T7300F/Q7300H dimensions in in. (mm).

Performance Specifications

Electrical Ratings:

Power: 20 to 30 Vac, 50/60 Hz.
System Current: 6 VA maximum at 30 Vac, 50 or 60 Hz.

Temperature Ratings:

Setpoint Range: Heating: 40°F to 90°F (4°C to 32°C;

Cooling: 45°F to 90°F (7°C to 32°C).

Operating: 40°F to 110°F (4°C to 43°C).
Shipping: -20°F to +130°F (-29°C to +54°C).
Display Accuracy: ±1°F (+0.5°C).

Differential:
2°F (1°C).

Humidity Ratings:
5% to 90% RH, noncondensing.

Input/Output Summary:

Table 2 summarizes the T7300F/Q7300H
Thermostat/Subbase inputs and outputs.

Advertising