General considerations – Honeywell Q7300H User Manual

Page 18

Advertising
background image

T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES

63-4365

18

General Considerations

Table 5 lists wiring types, sizes and distances for the T7300F/Q7300H and Excel 10 products. The Q73000H accepts 14
through 22 AWG (2.0 to 0.34 sq. mm wire).

Table 5. Field Wiring Reference Table.

Wire

Function

Recommended

Wire Size

(Minimum)

Construction

Specification

or Requirement

Vendor Wire Type

Distance

(Maximum)

Thermostat
wire.

Inputs: 18 AWG
(1.0 sq mm) five
wire cable bundle.

Standard thermostat
wire.

Honeywell AK3725
(US only), typical or
equivalent.

Thermostat
wire.

Outputs/Power:
14 to 18 AWG
(2.0 to
1.0 sq mm).

NEC Class 2, 140°F
(60°C) rating.

Level IV, 140°F
(60°C) rating.

Honeywell AK3752
(US only), typical or
equivalent.

LonWorks

Bus (Non-
Plenum).

22 AWG
(0.34 sq mm)

Twisted pair solid
conductor,
nonshielded or
Echelon® approved
cable.

Level IV, 140°F
(60°C) rating.

Honeywell AK3781
(one twisted pair),
AK3782 (two twisted
pair).

Refer to E-bus
Wiring guidelines
Users Guide
74-2865-1 for
maximum length.

Power
Wiring.

14 AWG
(2.0 sq mm)

Any pair nonshielded
(use heavier wire for
longer runs).

NEC Class II,
140°F (60°C)
rating.

Honeywell AK3754
(14 AWG) twisted
pair), AK3909
(14 AWG) single
conductor or
equivalent.

Limited by line-loss
effects on power
consumption.

Advertising