Cable termination, Singly terminated network segment – Honeywell Q7300H User Manual

Page 14

Advertising
background image

T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES

63-4365

14

M16085B

EXCEL 10

RI0

EXCEL 10

RI0

EXCEL 10

RI0

EXCEL 10

CVAHU

T7770

T7770

T7770

T7770

T7770

JACK FOR
OPERATOR
TERMINAL

209541B TERMINATION
MODULES (AT ENDS OF
LonWorks® BUS
DAISY-CHAIN)

T7770
WITH NO
LonWorks®
BUS ACCESS

T7770
WITH NO
LonWorks®
BUS ACCESS

LonWorks® BUS

I/O CONNECTIONS

EXCEL 10

RI0

EXCEL 10

RI0

EXCEL 10

CVAHU

EXCEL 10

RI0

EXCEL 10

RI0

EXCEL 10

CVAHU

1

4

8

12

16

17

23

30

31

37

44

EXCEL 15
W7760

BUILDING MANAGER

T7300

T7300

T7300

T7300

T7300

T7300

T7300

T7300

LonWorks® BUS

LonWorks®
BUS

LonWorks

®

BUS

Fig. 8. Wiring layout for one doubly terminated daisy-chain LonWorks

segment.

Cable Termination

The FTT network segment requires termination for proper
data transmission performance. Use a 209541B
Termination Module to connect two of the three termination
module wires to the LonWorks

Bus terminals.

Singly Terminated Network Segment

In a singly terminated topology segment, only one
termination is required and can be placed anywhere on the
segment. Singly terminated segments use the yellow and
brown wires. Mount the termination modules on the
appropriate terminals as shown in Fig. 9.

C1 C2 C3 C4 C5

EB EB

X

T

T AS

AS

ORANGE

BROWN

YELLOW

PART NO. 209541B
TERMINATION MODULE

M16202

Fig. 9. Singly terminated LonWorks

Bus termination

module.