T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES

9

63-4365

Table 2. Terminal descriptions and conditions.

Standard Terminal

Designations

Typical Connection

Function

Terminal Type

A1, A3

Damper control relay. See T7300F Installation Instructions, form
69-1025-3, installer setup 18, for control parameters.

Output

Dry contract

A2

Dry auxiliary contact. (A2 is common to A1, A3.)

Input

AS,AS

C7150B Discharge Air Sensor connection.

Input

B

Heating changeover valve.

Output

24V powered

contact

BM

ML7984 Actuator connection. No call for heat; valve closed
during occupied periods and open during unoccupied periods.

Output

C1, C2, C3, C4, C5

Communication input for T7147.

Input/Output

Low power

E

Emergency heat relay.

Output

24V powered

contact

EB, EB

LonWorks® Bus connection to LonWorks® network.

Input/output

Communications

FC

Fan control transformer.

Input

G

Fan relay.

Output

GH

High speed fan output. Activated during call for cooling.

Output

GL

Low speed fan output. Activated on call for heat and fan On
selection.

Output

O

Cooling changeover valve.

Output

P1, P2

Pump interlock relay. Operates circulator pump in hydronic heat
or energizes conventional heat system.

Input, output

R

24V system transformer.

Input

RC

24V cooling transformer.

Input

RH

24V heating transformer.

Input

RM

ML7984 Actuator connection. No call for heat; valve closed. Call
for stage 1 heat; valve approximately one-half open. Call for
stage 2 heat; valve fully open.

Output

T, T

Remote sensor input for T7047 or T7147.

Input

W1

Stage 1 heating relay or auxiliary heat relay.

Output

W2

Stage 2 heating relay

Output

W3

Stage 3 heating relay

Output

X

Heating transformer common.

Input

Y

Cool call.

24V output on Y

Y1

Stage 1 compressor contactor.

Output

Y2

Stage 2 cooling compressor (conventional). Stage 2
compressor contactor (heat pump).

Output

Y3

Stage 3 cooling compressor.

Output

Communications

The Q7300H provides networking capability in a
LonWorks® system when using a Free Topology
Transceiver (FTT) transformer-coupled communications
port running at 78 kilobits per second (kbs). The
transformer-coupled communications interface offers a
much higher degree of common-mode noise rejection
while ensuring dc isolation.

LonWorks® FTT networks are very flexible and convenient
to install and maintain, but it is imperative that the network
layout be carefully planned and accurate documentation
created and maintained. This aids in compliance

verification and future expansion of the network. It also
minimizes unknown or inaccurate wire run lengths, node-
to-node (device-to-device) distances, node counts, total
wire length, inaccurate repeater/router locations, and
misplaced or missing terminations. LonWorks® networks
can be configured in a variety of ways; refer to the E-Bus
FTT Network Wiring Guidelines, form 74-2865-1, for a
complete description of network topology rules and
maximum wire length. If longer runs are required, add a
Q7740A 2-way or Q7740B 4-way repeater to extend the
LonWorks® Bus length. Add a Q7751A to partition the
system into two segments to double the length of
LonWorks® Bus.