Warning, B. facing material – Heat & Glo Fireplace CERONA-36 User Manual

Page 36

Advertising
background image

Heat & Glo • Cerona-36, Cerona-42 • 2106-900 Rev. H • 11/08

36

B. Facing Material

Fire Risk.

Finish all edges and fronts to clearances and
specifi cations listed in manual.

• Black metal appliance front may be covered with

noncombustible material only.

• Do NOT overlap combustible materials onto appliance

front.

• Install combustible materials only up to specified

clearances on top, front and side.

• Seal joints between the fi nished wall and appliance top

and sides using only a 300º F minimum sealant.

Fire Risk.
Do NOT obstruct air inlet or outlet grilles.
Do NOT modify grilles.
• Modifying or covering grilles could cause
temperature rise and fi re hazard.

Finishing materials must not interfere with:
• Air fl ow through grilles or louvers.
• Operation of louvers or doors.
• Access for service.

Risk of Fire

• Non-combustible clearances MUST be

maintained.

• Sheetrock, wood or other combustibles must

NOT be used as sheathing or facing in the
non-combustible zone.

• See Section 11 for proper clearances.

• See Section 1 for combustible/non-

combustible defi nitions.

WARNING

WARNING

WARNING

Figure 11.4

A

B

C

Cerona-36

in.

49

16-3/4

43-5/8

mm

1245

425

1108

Cerona-42

in.

45-1/4

16-3/4

50-5/8

mm

1149

425

1286

Note: If using the Apollo Mantel System, the appliance must
be raised 1-1/4 in. from fl oor.

A

B

1 in.
(25)

C

CEILING

COMBUSTIBLE

SHEATHING

NON-COMBUSTIBLE
FACING MATERIAL
IN SHADED AREAS

FIREPLACE

ARCH OPENING

CLEARANCE
TO CEILING

MINIMUM

BOTTOM OF FIREPLACE
TO BOTTOM OF
NON-COMBUSTIBLE
FACING MATERIAL

Figure 11.3 Non-combustible Facing Material

A

B

Cerona-36

in.

43-5/8

50-3/16

mm

1108

1275

Cerona-42

in.

50-5/8

54-3/8

mm

1286

1381

A

B

NON-COMBUSTIBLE

FACING MATERIAL

1 in.

(25 mm)