Venting – Harman Coal Stoker VF3000 User Manual

Page 12

Advertising
background image

12

3-90-70741R13_05/13

Do not burn any fuel other than coal. Never use highly volatile

substances in your stove, such as gasoline, which could

cause an explosion.
When solid fuels are burned completely, they produce

water and carbon dioxide. However, in long slow burns, a

substantial amount of carbon monoxide may be produced.

If allowed to build up, carbon monoxide (which is odorless)

can prove fatally poisonous. Proper ventilation and draft will

prevent this from happening. If you smell smoke, thoroughly

ventilate your dwelling. Contact your dealer to arrange for

a draft test.
Other causes of poor ventilation or draft are icing, exhaust

fans, a blocked outside air inlet, and room air starvation. If

your stove is sluggish and you get occasional odor, check

these possibilities and increase the air flow in your home.
Installing to a Prefabricated Chimney
When venting your stove using a prefabricated chimney,

be sure to contact local building code authorities, and to

follow the manufacturer’s instructions exactly. Use only

the manufacturer’s parts; do not use makeshift installation

techniques. All prefabricated chimneys must be tested to

either the U.S. or Canadian high-temperature standards, UL

103 or ULC S629.

do not connect the venting to any air distribution duct or

system

existing Masonry Chimneys
If you plan on using a pre-existing masonry chimney, have

it thoroughly inspected and cleaned. Any faults which make

the chimney unsafe and unusable must be repaired prior to

use. These can include improper height, structural defects,

blockages, inadequate clearance to combustibles, unsealed

openings into other rooms of the house, signs of creosote or

smoke leakage, a loose or absent clean-out door, or absence

of a liner.
Venting to a Masonry Chimney
When connecting to a masonry chimney, several provisions

are standard. First, whether the chimney connector is vented

to the chimney through a thimble or a breech pipe, neither

must pass beyond the inner surface of the chimney liner,

and both must be firmly cemented in place with refractory

cement. (A thimble is a masonry pipe which is inserted

through the chimney wall, and is frequently the preferred

method; a breech pipe is a piece of steel pipe used the same

way.) In Canada, a breech pipe has ridges or protrusions to

lock it firmly into the refractory cement. In either case, the

chimney connector vents to the chimney through the thimble

or breech pipe.
Using a thimble, the connector slides completely inside the

masonry to the inner edge of the flue liner, and may be easily

removed for chimney and connector inspection. A breech

pipe must extend at least 2” (50 mm) into the room, so the

connector can be attached with sheetmetal screws.
Venting to a Masonry Fireplace Chimney
In some situations, a code compliant chimney originally

used for a masonry fireplace may be used to install your

stove. In addition to the requirements found in the previous

paragraphs, it is important to be aware that all clearances

must be met, including those from the chimney connector to

combustibles. Do not forget to include floor protection in your

plans. (See Clearances and Floor Protection in this section.)

Since many fireplaces have exposed wooden mantels and

trim, pay special attention to the clearances necessary to

these materials.
If your fireplace chimney is behind a combustible wall, you

must use an approved wall pass-through system to gain

access to the masonry chimney. The chimney connector

must enter the chimney at a place where it is lined, and

the fireplace must be made inoperable. For example, you

might remove the damper, replacing it with a secure, airtight,

noncombustible seal (removable for inspection); this also

satisfies the requirement that no room air must be allowed

to enter the chimney.

Venting

Advertising
This manual is related to the following products: