Honeywell ST 3000 SMART TRANSMITTER STR93D User Manual

Page 7

Advertising
background image

34-ST-03-57

Page 7


Note: A minimum of 250 ohms
of loop resistance is necessary
to support communications.
Loop resistance equals barrier
resistance plus wire resistance
plus receiver resistance.

= Operating Area

0 10.8 16.28 20.63 25 28.3 37.0 42.4

1440

1200

800

650

450

250

Operating Voltage (Vdc)

Loop

Resistance

(ohms)

Note: A minimum of 250 ohms
of loop resistance is necessary
to support communications.
Loop resistance equals barrier
resistance plus wire resistance
plus receiver resistance.

= Operating Area

0 10.8 16.28 20.63 25 28.3 37.0 42.4

1440

1200

800

650

450

250

Operating Voltage (Vdc)

Loop

Resistance

(ohms)

Figure 14—Supply voltage and loop resistance chart

Performance Under Rated Conditions * - Model STR93D (0 to 100 psi/7 bar)

Parameter

Description

Upper Range Limit

psi

bar

100 (Transmitter URL or maximum seal pressure rating, whichever is lower.)
7

Minimum Span

psi

bar

0.9
0.063

Turndown Ratio

110 to 1

Zero Elevation and Suppression No limit except minimum span within ±100% URL.

Accuracy (Reference – Includes
combined effects of linearity,
hysteresis, and repeatability)

Accuracy includes residual error

after averaging successive
readings.

For F

OUNDATION

Fieldbus use

Digital Mode specifications. For
HART use Analog Mode
specifications.

In Analog Mode: ±0.20% of calibrated span or upper range value (URV), whichever is
greater, terminal based.
For URV below reference point (50 inH2O), accuracy equals:

±0.10 + 0.10

50 inH2O

span inH2O

or ±0.10 + 0.10

(

)

125 mbar

span mbar in % of span

In Digital Mode: ±0.175% of calibrated span or upper range value (URV), whichever
is greater, terminal based.
For URV below reference point (50 inH2O), accuracy equals:

±0.075 + 0.10

50 inH2O

span inH2O

or ±0.075 + 0.10

(

)

125 mbar

span mbar in % of span

Combined Zero and Span
Temperature Effect per 28°C
(50°F) **

In Analog Mode: ±1.5% of span.

For URV below reference point (200 inH2O), effect equals:

±0.30 + 1.2

200 in H

2

O

span in H

2

O

or ±0.30 + 1.2

500 mbar

span mbar

In % span

±0.30 + 1.2

200 in H

2

O

span in H

2

O

200 in H

2

O

span in H

2

O

or ±0.30 + 1.2

500 mbar

span mbar

500 mbar

span mbar

In % span

In Digital Mode:

±1.475% of span.

For URV below reference point (200 inH2O), effect equals:

±0.275 + 1.2

200 in H

2

O

span in H

2

O

or ±0.275 + 1.2

500 mbar

span mbar

In % span

±0.275 + 1.2

200 in H

2

O

span in H

2

O

200 in H

2

O

span in H

2

O

or ±0.275 + 1.2

500 mbar

span mbar

500 mbar

span mbar

In % span

* Performance specifications are based on reference conditions of 25°C (77°F), zero (0) static pressure, 10 to 55% RH, and
316L Stainless Steel barrier diaphragm.
** Specification applies to transmitters with 2 seals only. Apply 1.5 times factor to temperature effect for capillary lengths greater than 10 feet
or for 2-inch sanitary seals.