S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

12

STARTING THE S7999C OI
DISPLAY

Power-up Validation

The Home page will appear and the “Power” LED will be on

continuously and the “COM” LED will be blinking when the

device is properly powered and communicating to the Sola

Control.

The “COM” LED exists for I/O traffic.

1. Make sure the LED is blinking.

2. If the LED is not blinking:

a. Make sure the proper connections have been made

between the display and the Sola Control.

b. See “Wiring (S7999C OI Display)” on page 10 for

proper wiring of the display connections.

Fig. 13. S7999C display page flow.

PAGE NAVIGATION

The Sola OI Displays present information and options in a

paged manner. Pages are displayed in a tree structure in which

the user navigates up and down to arrive at the desired

Function (see Fig. 8 for S7999B or Fig. 13 for S7999C). The

page descriptions are provided below so that you can

understand the purpose of each and view the selections,

parameters, and information that is available or required on

each.

Common OI Display Page Symbols

Most pages have a Home button

in the top-left corner of

the screen and a Back button

in the top-right corner of

the screen. The Home button returns the user to the Home

page and terminates any operation in progress. The Back

button returns the user to the previous page.

Two other icons may be noticed near the boiler name.

A bell

will be displayed if the system is in Lockout that

reset will be required.

A padlock

will be shown on screens that require a password

to change the parameter. An unlocked padlock indicates the

password has been entered to change the parameter.

Status or Home Page

A status (summary) page (Fig. 14) is displayed when the

S7999C display is connected. This status page appears on the

S7999B when the Sola control icon is pressed on the “Home”

page. The status page displays the current condition of the

burner control and displays some of the more important

configuration settings.

The boiler name associated with the burner control is

displayed in the title on the status page.

NOTE: When the burner control has no boiler name defined,

Modbus address is used to identify the boiler.

The initial status page displayed contains summary status

information as shown in Fig. 14. Any status information not

applicable for the installation is grayed/blanked out on the

screen.

Buttons on this screen include:

Configure: used to configure the burner control (see

“Configure Button” on page 13 for more details).

Operation: used to perform daily or frequent functions with

the burner control, such as setpoint adjustment, etc. See

“Operation Button” on page 18 for details.

Diagnostic: used to view burner control diagnostic

information (see “Diagnostics Button” on page 19 for more

details).

Details: used to view burner control detail status

information (see “Details” on page 38).

HOME

PAGE

M29774

LOGIN

CONFIGURE

CONFIGURATION

GROUPS

LOGOUT

VERIFY

DISPLAY

SETUP

OPERATION

CH

LOGIN

DHW

DIAGNOSTICS

DIAGNOSTIC

TEST

BURNER

CONTROL

DIGITAL I/O

ANALOG I/O

PROGRAM

MODULE

CLEAN

SCREEN

SYSTEM

CONFIGURATION

ADVANCED

SETUP

DETAILS

HISTORY

ALERTS

DIAGNOSTIC

ANALYSIS

HISTORY

OK

LOCKOUTS

ALERTS

SILENCE

MODULATION

SETPOINTS

PUMPS

?

KEY

BUTTON FLOW

BACK ICON FLOW

HOME ICON ALWAYS

TAKES YOU TO THE

HOME PAGE

ANNUNCIATION