S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

65-0303—05

38

DETAILS

Details of the hydronic or steam system is accomplished

through the detail status pages. The detail status page is

shown below.

Screens will appear only if they are configured for your system.

Information shown is current status. For example: firing rate is

the current fan speed or motor position; timing shown is current

time Sola is at.

Fig. 70. Hydronic CH detail status page.

Status information on the detail status page is organized into

groups and displayed on the page one group at a time. The

user moves from one group to another using the left and right

arrow buttons.

Status data on the detail status page is displayed in a menu for

the group that is currently displayed. If more status items exist

in the group than will fit on the screen, a vertical scroll bar

allows the user to see all status data. If the user selects a line

of status data in the menu, it will expand in bigger, more easily

readable text, as show in Fig. 71. Additional information about

Status data and groups that are displayed are provided in the

R7910A or R7911 Status section of this document.

Fig. 71. Hydronic “expanded” detail status.

R7910A or R7911 Status

Data in Tables 45–Table 56 are displayed on the R7910A

Hydronic or R7911 Steam status pages. A complete list of

Status tables can be found in Table 60 on page 53.

The CH status data shown in Table 45 displays first when the

CH Hydronic heating loop is selected on the Home page.

Fig. 72. CH Hydronic Status menu (top).

Table 45. CH Hydronic Status.

Data Comment

CH enable

Enabled, Disabled

CH burner demand

On or Off

CH pump

On or Off

CH pump demand

On or Off

CH pump overrun

time

Running overtime for CH pump

(seconds)

CH requested rate

RPM or %

CH OFF setpoint

Setpoint plus hysteresis

CH setpoint

Temp setting between -40 °F to 266 °F

(-40 °C to 130 °C)

CH ON setpoint

Setpoint minus hysteresis

CH setpoint source

Normal, TOD, Outdoor reset, Remote

control

CH status

Disabled, Normal, Suspended

Demand source

Sensor only, Sensor and Stat terminal,

Sensor and Remote Stat, LCI and

sensor

Outlet high limit

Yes or No

Outlet high limit

setpoint

Temp setting between -40 °F to 266 °F

(-40 °C to 130 °C)

Outlet sensor state

None, Normal, Open, Shorted,

Outside high range, Outside low

range, Not reliable (None = no outlet

sensor)

Outlet temperature

Outlet temperature (same as bar

graph)