Display reset, Parameters, S7999b only – Honeywell Local Operator Interface S7999B User Manual

Page 53

Advertising
background image

53

65-0303—05

Fig. 118. COM1 tab.

S7999B Only

COM2 is a Modbus gateway for Building Automation System (BAS)

networking.

Press the COM2 tab (see Fig. 119) to define settings:

Enable Modbus Gateway: This box must be selected to enable

the COM2 BAS interface.

Modbus Gateway Speed: Select the baud rate (38400, 19, 200,

or 9600 bps)

Modbus Gateway Timeout: Defines how long the BAS will wait

after sending a Modbus message before timing out and sending

the next modbus message (currently non-functional; leave at 1.0)

Fig. 119. COM 2 tab.

Display Reset

The user can reset the display and force a power-up by pressing the

Display Reset button. A pop-up dialog box confirming the reset

request displays (Fig. 120) before the reset proceeds.

Fig. 120. Processor Reset.

When the Display is reset, the display will reboot and automatically

seek out the Modbus™ device connected to it. When the search is

complete, the display will return to the home page.

Parameters

A complete list of configurable parameters is shown in Table 61.

Table 60. Status Tables.

Name

Table #

Page #

CH

45

38

DHW

46

39

Burner Control

47

40

Demand and Modulation

48

41

Inlet High Limit

49

41

Fan

50

42

Pump

51

42

Flame Detection

52

42

Statistics

53

43

Stack Limit

54

43

Lead Lag Slave

55

43

Lead Lag Master

56

44

Table 61. Configurable Parameters.

Parameter

Comment

Table

#

Page

#

Boiler Name Name to identify boiler (up to 20

characters)

6

21

Installation

Notes regarding installation (up

to 20 characters)

Installer

password

Change installer password

setting

OEM

password

Change OEM password setting

Factory Data OEM name to associate with

boiler (up to 20 characters)