Dhw storage configuration, Dhw plate heat exchanger configuration – Honeywell Local Operator Interface S7999B User Manual

Page 23

Advertising
background image

S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE

23

65-0303—05

Domestic Hot Water (DHW)
Configuration Parameters
(R7910A Hydronic Control Only)

Table 11 displays Domestic Hot Water (DHW) configuration

parameters.

Fig. 41. Domestic Hot Water (DHW) configuration.

DHW Storage Configuration

Table 12 displays DHW Storage configuration parameters.

DHW Plate Heat Exchanger
Configuration

Table 13 displays DHW Plate Heat Exchanger configuration

parameters.

Table 11. Domestic Hot Water (DHW)

Configuration Parameters.

Parameter

Comment

Enable

Disable or Enable Domestic Hot

Water Loop

Demand switch

Sensor for Central Heat demand:

DHW sensor only,

DHW sensor & Remote Stat,

DHW switch & inlet sensor, or

DHW switch & outlet sensor

Priority source

Which system has priority:

Disabled or

Heat Demand

Priority method

Boost during priority time

Drop after priority time

Modulation sensor

DHW Sensor

Outlet Sensor

Inlet Sensor

Auto: DHW (S6) or Inlet Sensor

Auto: DHW (S6) or Outlet Sensor

Setpoint

-40 °F to 240 °F (-40 °C to 115 °C)

Time of day setpoint Setpoint when Time Of Day switch is

on. -40 °F to 240 °F (-40 °C to 115 °C)

Off hysteresis

Differential above setpoint when boiler

is turned off. -40 °F to 240 °F (-40 °C

to 115 °C)

On hysteresis

Differential from setpoint when boiler

is turned on.

2 °F to 234 °F (-16 °C to 112 °C)

DHW priority

override time

___hour ___min ___sec

Hysteresis step

time

___hour ___min ___sec

DHW priority vs CH Which system has priority:

Central Heat over Domestic Hot

Water, or

Domestic Hot Water over Central Heat

DHW priority vs

Lead Lag

Which system has priority:

Lead Lag over Domestic Hot Water,

Domestic Hot Water over Lead Lag

DHW P-gain

Gain applied for the P portion of the

PID equation

0-400

DHW I-gain

Gain applied for the I portion of the

PID equation

0-400

DHW D-gain

Gain applied for the D portion of the

PID equation

0-400

Table 12. DHW Storage Configuration Parameters.

Parameter

Comment

DHW storage

enable

Enabled, Disabled

Storage time

___hour ___min ___sec

Setpoint

-40 °F to 266 °F (-40 °C to 130 °C)

Off hysteresis

-0 °F to 180 °F (-17 °C to 82 °C)

On hysteresis

-0 °F to 180 °F (-17 °C to 82 °C)

Table 13. DHW Plate Heat Exchanger

Configuration Parameters.

Parameter

Comment

Tap detect degrees -0 °F to 180 °F (-17 °C to 82 °C)
Tap detect on

recognition time

___hour ___min ___sec

Tap detect on

threshold

-0 °F to 180 °F (-17 °C to 82 °C)

Tap detect minimum

on time

___hour ___min ___sec

Tap stop inlet-DHW

degrees

-0 °F to 180 °F (-17 °C to 82 °C)

Tap stop outlet-Inlet

degrees

-0 °F to 180 °F (-17 °C to 82 °C)

Table 11. Domestic Hot Water (DHW)

Configuration Parameters. (Continued)

Parameter

Comment